Related parameters – Yaskawa G7 Drive User Manual

Page 271

Advertising
background image

6

-54

‹

Motor Overheating Protection Using PTC Thermistor Inputs

Perform motor overheating protection using the thermistor temperature resistance characteristics of the PTC
(Positive Temperature Coefficient) built into the windings of each motor phase.

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L1-03

Motor
Overheat
Alarm
Operation
Selection

Sets operation selection when the
motor temperature analog input
(H3-09 = E) exceeds the OH3
alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

No

A

A

A

A

A

MOL Thm
Input

L1-04

Motor
Overheat
Fault
Operation
Selection

Sets stopping method when the
motor temperature analog input
(H3-09 = E) exceeds the OH4 fault
level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

1

No

A

A

A

A

A

MOL Filter
Time

L1-05

Motor
Temperature
Input Filter
Time

This parameter adjusts the filter on
the motor temperature analog input
(H3-09 = E). Increase to add
stability, decrease to improve
response.

0.00

to

10.00

0.20sec

No

A

A

A

A

A

MOL Filter
Time