Hunting-prevention function, Related parameters, Hunting-prevention function -37 – Yaskawa G7 Drive User Manual

Page 254

Advertising
background image

Improved Operating Efficiency

6-

37

‹

Hunting-prevention Function

The hunting-prevention function suppresses hunting when the motor is operating with a light load. This func-
tion can be used in V/f without PG and V/f with PG.

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

n1-01

Hunting
Prevention
Selection

If the motor vibrates while lightly
loaded, hunting
prevention may reduce the
vibration.
0: Disabled
1: Enabled

0 or 1

1

No

A

A

No

No

No

Hunt Prev
Select

n1-02

Hunting
Prevention
Gain Setting

Sets the gain for the Hunting
Prevention Function.
If the motor vibrates while lightly
loaded and n1-01=1, increase the
gain by 0.1 until vibration ceases.
If the motor stalls while n1-01=1,
decrease the gain by 0.1 until the
stalling ceases.

0.00

to

2.50

1.00

No

A

A

No

No

No

Hunt Prev Gain

Advertising