Adjusting frequency references, Adjusting analog frequency references, Related parameters – Yaskawa G7 Drive User Manual

Page 241: Adjusting frequency references -24, Adjusting analog frequency references -24

Advertising
background image

6

-24

Adjusting Frequency References

This section explains methods of adjusting frequency references.

‹

Adjusting Analog Frequency References

Gain and bias are among the parameters used to adjust analog inputs.

„

Related Parameters

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

H3-01

Terminal A1
Signal Level
Selection

Sets the signal level of terminal
A1.
0: 0 to 10Vdc
1: -10 to +10Vdc
[11-bit plus polarity sign]

0 or 1

0

No

A

A

A

A

A

Term A1 Lvl
Sel

H3-02

Terminal A1
Gain Setting

Sets the output level when 10V

is input, as a percentage of the
maximum output frequency

(E1-04).

0.0

to

1000.0

100.0%

Yes

A

A

A

A

A

Terminal A1
Gain

H3-03

Terminal A1
Bias Setting

Sets the output level when 0V is
input, as a percentage of the
maximum output frequency
(E1-04).

-100.0

to

100.0

0.0%

Yes

A

A

A

A

A

Terminal A1
Bias

H3-04

Terminal A3
Signal Level
Selection

Sets the signal level of terminal
A3.
0: 0 to 10Vdc
1: -10 to +10Vdc

0 or 1

0

No

A

A

A

A

A

Term A3 Signal

H3-05

Terminal A3
Function
Selection

[Refer to table "H3-05, H3-09
Settings" for multi-function
selections]

0 to 1F

2

No

A

A

A

A

A

Terminal A3
Sel

H3-06

Terminal A3
Gain Setting

Sets the output level when 10V is

input.

0.0

to

1000.0

100.0%

Yes

A

A

A

A

A

Terminal A3
Gain

H3-07

Terminal A3
Bias Setting

Sets the frequency reference

when 0V is input.

-100.0

to

100.0

0.0%

Yes

A

A

A

A

A

Terminal A3
Bias

Advertising