Setting precautions – Yaskawa G7 Drive User Manual

Page 245

Advertising
background image

6

-28

Fig 6.27 Jump Frequency

„

Setting Jump Frequency Reference Using an Analog Input

When parameter H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-func-
tion Analog Input Terminal A3 Function Selection) is set to A (jump frequency), you can change the jump fre-
quency using the terminal A2 input level.

Fig 6.28 Jump Frequency Setting Using an Analog Input

„

Setting Precautions

Set the jump frequency according to the following formula: d3-01

≥ d3-02 ≥ d3-03 > Analog input.

When parameters d3-01 to d3-03 are set to 0Hz, the jump frequency function is disabled.

Output frequency

Jump frequency reference

Jump

frequency

width d3-04

Jump

frequency

3 (d3-03)

Jump

frequency

2 (d3-02)

Jump

frequency

1 (d3-01)

Frequency reference descending

Frequency

reference
ascending

Jump

frequency

width d3-04

Jump frequency width d3-04

Jump frequency

0 V

(4 mA)

Multi-function analog input
terminal A2 or A3 input level

10 V

(20 mA)

Max. output frequency

E1-04