Input fuses – Yaskawa G7 Drive User Manual

Page 436

Advertising
background image

Conformance to UL and CE Markings

10-

13

Input Fuses

In order to conform to the Low Voltage Directive or UL, fuses must be provided for inputs. Use UL-compatible
input fuses with ratings higher than the voltages and currents, and fusing I

2

t specifications within the ranges

shown in the table below.

Table 10.2 Selection Requirements for Input Fuses with Examples

Voltage

Class

Drive Model

Number

CIMR-G7U

Selection Requirements

Input Fuse (Examples)

Voltage

(V)

Current

(A)

Fusing I

2

t

(A

2

sec)

Model Number Manufacturer Ratings

Fusing

I

2

t

(A

2

sec)

200-240

V class

20P4

240

10

12 to 25

A60Q12-2

FERRAZ

600 V

12 A

17

20P7

240

15

23 to 55

CR2LS-20/UL

FUJI

600 V

12 A

27

21P5

240

20

34 to 98

CR2LS-30/UL

FUJI

250 V

20 A

60

22P2

240

30

82 to 220

CR2LS-50/UL

FUJI

250 V

30 A

200

23P7

240

40

220 to 610

CR2LS-75/UL

FUJI

250 V

50 A

560

25P5

240

50

290 to 1300

CR2LS-75/UL

FUJI

250 V

75 A

560

27P5

240

60

450 to 5000

CR2LS-100/UL

FUJI

250 V

75 A

810

2011

240

90

1200 to 7200

CR2L-125/UL

FUJI

250 V
100 A

1570

2015

240

120

1800 to 7200

CR2L-150/UL

FUJI

250 V
125 A

2260

2018

240

140

870 to 16200

CR2L-150/UL

FUJI

250 V
150 A

2260

2022

240

160

1500 to 23000

CR2L-200/UL

FUJI

250 V
150 A

4010

2030

240

220

2100 to 19000

CR2L-260/UL

FUJI

250 V
200 A

7320

2037

240

270

2700 to 55000

CR2L-300/UL

FUJI

250 V
260 A

9630

2045

240

300

4000 to 55000

CR2L-300/UL

FUJI

250 V
300 A

9630

2055

240

370

7100 to 64000

CR2L-400/UL

FUJI

250 V
350 A

24000

2075

240

500

11000 to 64000

CR2L-500/UL

FUJI

250 V
450 A

40000

2090

240

600

13000 to 83000

CR2L-600/UL

FUJI

250 V
600 A

52000

2110

240

700

13000 to 83000

A50P700-4

FERRAZ

250 V
600 A

49000

Advertising