Run command, Selecting the run command source, Related parameters – Yaskawa G7 Drive User Manual

Page 224: Performing operations using a digital operator, Performing operations using a 2-wire sequence, Run command -7

Advertising
background image

Run Command

6-

7

Run Command

This section explains input methods for the run command.

‹

Selecting the Run Command Source

Set parameter b1-02 to select the source for the run command.

„

Related Parameters

„

Performing Operations Using a Digital Operator

When b1-02 is set to 0, you can perform Drive operations using the Digital Operator keys (RUN, STOP, JOG,
and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes.

„

Performing Operations Using Control Circuit Terminals

When b1-02 is set to 1, you can perform Drive operations using the control circuit terminals.

Performing Operations Using a 2-wire Sequence

The factory setting is set to a 2-wire sequence. When control circuit terminal S1 is set to ON, forward operation
will be performed, and when S1 is turned OFF, the Drive will stop. In the same way, when control circuit termi-
nal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the Drive will stop.

Fig 6.8 2-wire Sequence Wiring Example

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open-

loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b1-02

Run
Command
Selection

Selects the run command input source.
0: Operator - RUN and STOP keys on

Digital Operator.

1: Terminals - Contact closure on

terminals S1 or S2.

2: Serial Com - Modbus RS-422/485

terminals R+, R-, S+, and S-.

3: Option PCB - Option board connected

on 2CN.

0 to 3

1

No

Q

Q

Q

Q

Q

Run Source

Drive

Forward/stop

Reverse/stop

Sequence common