Connection example and time chart – Yaskawa G7 Drive User Manual

Page 223

Advertising
background image

6

-6

Setting Precautions

When setting analog inputs to step 1 to step 3, observe the following precautions.

When setting terminal A1's analog input to step 1, set b1-01 to 1, and when setting d1-01 (Frequency Ref-
erence 1) to step 1, set b1-01 to 0.

When setting terminal A2's analog input to step 2, set H3-09 to 2 (auxiliary frequency reference). When
setting d1-02 (Frequency Reference 2) to step 2, set H3-09 to 1F (do not use analog inputs).

When setting terminal A3's analog input to step 3, set H3-05 to 3 (auxiliary frequency reference 2). When
setting d1-03(Frequency Reference 3) to step 3, set H3-05 to 1F (Analog input not used).

„

Connection Example and Time Chart

The following diagram shows a time chart and control circuit terminal connection example during a 9-step
operation.

Fig 6.6 Control Circuit Terminal During 9-step Operation

Fig 6.7 Multi-step speed reference/Jog Frequency Selection Time Chart

Drive

S1 Forward/stop

S2 Reverse/stop

S3 External fault

S4 Fault reset

S5 Multi-step speed reference 1

S6 Multi-step speed reference 2

S7 Multi-step speed reference 3

SC Sequence common

S8 Jog frequency

Forward/stop

Multi-step speed
reference 1

Multi-step speed
reference 2
Multi-step speed
reference 3
Jog frequency
selection

Frequency

reference 3

Frequency

reference 4

Frequency

reference 5

Frequency

reference 6

Jog frequency

Frequency

reference 8

Frequency

reference 7

Frequency

reference

Frequency

reference 1:

Master speed

frequency

Frequency

reference 2:

Auxiliary speed

frequency