480vac drives – Yaskawa G7 Drive User Manual

Page 215

Advertising
background image

5

-104

„

380-480Vac Drives

Parameter

Number

Name

Unit

Factory Setting

-

Drive Capacity

kW

0.4

0.75

1.5

2.2

3.7

4.0

5.5

7.5

11

15

o2-04

kVA selection

-

20

21

22

23

24

25

26

27

28

29

b8-03

Energy Saving Control
Filter Time Constant

s

0.50 (Open-loop vector control)

b8-04

Energy Saving
Coefficient Value

-

576.40 447.40 338.80 313.60 245.80 236.44 189.50 145.38 140.88 126.26

C6-02

Carrier Frequency
Selection

*1

-

3

3

3

3

3

3

3

3

3

3

C6-11

Carrier Frequency
Selection for Open Loop
Vector 2

*2

-

3

3

3

3

3

3

3

3

3

3

-

Carrier frequency
selection upper limit

-

3

3

3

3

3

3

3

3

3

3

E2-01

(E4-01)

Motor Rated Current

A

1.00

1.60

3.10

4.20

7.00

7.00

9.80

13.30

19.9

26.5

E2-02

(E4-02)

Motor Rated Slip

Hz

2.90

2.60

2.50

3.00

2.70

2.70

1.50

1.30

1.70

1.60

E2-03

(E4-03)

Motor No-Load Current

A

0.60

0.80

1.40

1.50

2.30

2.30

2.60

4.00

5.6

7.6

E2-05

(E4-05)

Motor Line-to-Line
Resistance

Ω

38.198 22.459 10.100 6.495

3.333

3.333

1.595

1.152

0.922

0.550

E2-06

(E4-06)

Motor Leakage
Inductance

%

18.2

14.3

18.3

18.7

19.3

19.3

18.2

15.5

19.6

17.2

E2-10

Motor Iron Loss for
Torque Compensation

W

14

26

53

77

130

130

193

263

385

440

L2-02

Momentary Power Loss
Ride-thru Time

s

0.1

0.2

0.3

0.5

0.5

0.8

0.8

1.0

2.0

2.0

L2-03

Momentary Power Loss
Minimum Base Block
Time

s

0.2

0.3

0.4

0.5

0.6

0.6

0.7

0.8

0.9

1.0

L2-04

Momentary Power Loss
Voltage Recovery Ramp
Time

s

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.6

L8-02

Overheat Alarm Level

°C

95

95

95

95

95

95

95

90

95

95

n5-02

Motor Acceleration Time

s

0.178

0.142

0.166

0.145

0.154

0.154

0.168

0.175

0.265

0.244