UL Markings

The G7 is UL listed to UL Standard 508C, UL FILE No.: E13145.

‹

Conformance to UL Standard

To comply with UL standard, follow the appropriate installation instructions.

„

Installation Site

Install the Inverter in a pollution degree 2 environment or equivalent.

„

Specification of Closed-Loop Connector

The closed-loop connectors must be installed on conductors before installing to terminal blocks.

Use UL Listed closed-loop connectors shown in Table 10.5 below.

Table 10.5 JST Closed-Loop Connector Model

Inverter

Model CIMR-G7

JST Kit P/N

Input

Wire Size

Input

JST Kit P/N

Output

Wire Size

Output

JST Kit P/N

2015

2 AWG

38-8

4 AWG

22-8

2018

2 AWG

38-8

2 AWG

38-8

2022

1/0 AWG

60-8

1/0 AWG

60-8

2030

3/0 AWG

80-10

3/0 AWG

80-10

2037

4/0 AWG

100-10

4/0 AWG

100-10

2045

1/0 AWG

60-10 (2 per Ph)

1/0 AWG

60-10 (2 per Ph)

2055

3/0 AWG

80-10 (2 per Ph)

3/0 AWG

80-10 (2 per Ph)

2075

250 kcmil

150-12 (2 per Ph)

4/0 AWG

100-12 (2 per Ph)

2090

400 kcmil

200-12 (2 per Ph)

250 kcmil

150-12 (2 per Ph)

2110

400 kcmil

200-12 (2 per Ph)

300 kcmil

150-12 (2 per Ph)

4018

6 AWG

14-6

6 AWG

14-6

4022

4 AWG

22-6

4 AWG

22-6

4030

2 AWG

38-8

4 AWG

22-8

4037

2 AWG

38-8

2 AWG

38-8

4045

1/0 AWG

60-8

1/0 AWG

60-8

4055

3/0 AWG

80-10

3/0 AWG

80-10

4075

4/0 AWG

100-10

4/0 AWG

100-10

4090

1/0 AWG

60-10 (2 per Ph)

1/0 AWG

60-10 (2 per Ph)

4110

3/0 AWG

80-10 (2 per Ph)

3/0 AWG

80-10 (2 per Ph)

4132

3/0 AWG

80-12 (2 per Ph)

3/0 AWG

80-12 (2 per Ph)

4160

4/0 AWG

100-12 (2 per Ph)

4/0 AWG

100-12 (2 per Ph)

4185

250 kcmil

150-16 (2 per Ph)

250 kcmil

150-16 (2 per Ph)

4220

400 kcmil

200-16 (2 per Ph)

300 kcmil

150-16 (2 per Ph)

4300

650 kcmil

325-16 (2 per Ph)

650 kcmil

325-16 (2 per Ph)

Advertising