Yaskawa G7 Drive User Manual

Page 297

Advertising
background image

6

-80

*

1

In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, the bias amount is added and then output.

See H4-02 when stopped in Quick, Advanced, or Verify mode. If 03 appears on the setting screen, then terminal FM is used.
See H4-04 when stopped in Quick, Advanced, or Verify mode. If 06 appears on the setting screen, then terminal AM is used.

*

2

Setting "2: 4 to 20mA" is not available in F7A

*

3

In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, and the bias amount is added and then output.

See F4-02 when stopped in Quick, Advanced, or Verify mode. If 05 appears on the setting screen, then CH1 is used.
See F4-04 when stopped in Quick, Advanced, or Verify mode. If 06 appears on the setting screen, then CH2 is used.

F4-01

AO-08/AO-
12 Channel 1
Monitor
Selection

Sets the number of the monitor item
to be output. (U1-oo)
The following settings cannot be
used:
4, 10 to 14, 25, 28, 29, 30, 34, 35,
39, 40, 41.

1 to 45

2

No

A

A

A

A

A

AO Ch1
Select

F4-02

AO-08/AO-
12 Channel 1
Gain

Sets the channel 1 gain.
Ex: Set F4-02 = 50% to output
100% at 5.0V output.

0.00

to

1000.0

100.0%

Yes

A

A

A

A

A

AO Ch1 Gain

F4-03

AO-08/AO-
12 Channel 2
Monitor
Selection

Sets the number of the monitor item
to be output. (U1-xx)
The following settings cannot be
set:
4, 10 to 14, 25, 28, 29, 30, 34, 39,
40, 41.

1 to 45

3

No

A

A

A

A

A

AO Ch2
Select

F4-04

AO-08/AO-
12 Channel 2
Gain

Sets the channel 2 gain. *

3

Ex: Set F4-04 = 50% to output
100% at 5.0V output.

0.00

to

1000.0

50.0%

Yes

A

A

A

A

A

AO Ch2 Gain

F4-05

AO Ch1 Bias Sets the channel 1 bias (100%/10V).

Ex: Set F4-05 = 50% to output 0%
at 5.0V output.

-110.0

to

110.0

0.0%

Yes

A

A

A

A

A

AO Ch1 Bias

F4-06

AO Ch2 Bias Sets the channel 2 bias (100%/10V).

Ex: Set F4-06 = 50% to output 0%
at 5.0V output.

-110.0

to

110.0

0.0%

Yes

A

A

A

A

A

AO Ch2 Bias

F4-07

AO-12
Channel 1
Signal Level

Sets the range of the voltage
output.
0: 0 to 10Vdc
1: -10 to +10Vdc

0 to 1

0

No

A

A

A

A

A

AO Opt
Level Sel

F4-08

AO-12
Channel 2
Signal Level

Sets the range of the voltage
output.
0: 0 to 10Vdc
1: -10 to +10Vdc

0 to 1

0

No

A

A

A

A

A

AO Opt
Level Sel

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2