Fault Trace: U2

User parameters for error tracing are shown in the following table

.

Parameter

Number

Name

Description

Output Signal

Level During

Multi-Function

Analog Output

Min.

Unit

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

U2-01

Current Fault

Description of current fault.

No output possible.

-

A

A

A

A

A

80H

Current Fault

U2-02

Previous
Fault

Desscription of most recent fault.

-

A

A

A

A

A

81H

Last Fault

U2-03

Frequency
Reference at
Previous
Fault

Gives the frequency reference at
the most recent fault.

0.01

Hz

A

A

A

A

A

82H

Frequency
Ref

U2-04

Output
Frequency at
Previous
Fault

Shows the output frequency at
the most recent fault.

0.01

Hz

A

A

A

A

A

83H

Output Freq

U2-05

Output
Current at
Previous
Fault

Gives the output current at the
most recent fault.

0.1 A

A

A

A

A

A

84H

Output
Current

U2-06

Motor Speed
at Previous
Fault

Shows the motor speed at the
most recent fault.

0.01

Hz

No

A

A

A

A

85H

Motor Speed

U2-07

Output
Voltage at
Previous
Fault

Gives the output voltage at the
most recent fault.

0.1 V

A

A

A

A

A

86H

Output
Voltage

U2-08

DC Bus
Voltage at
Previous
Fault

Shows the DC BUS voltage at
the most recent fault.

1 V

A

A

A

A

A

87H

DC Bus
Voltage

U2-09

Output Power
at Previous
Fault

Gives the output power at the
most recent fault.

0.1

kW

A

A

A

A

A

88H

Output
kWatts