Performing Speed Control with PG

This section explains functions with V/f control with PG.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

F1-01

PG parameter

Sets the number of pulses per rev-
olution (PPM) of the encoder
(pulse generator).

0

to

60000

600

No

No

Q

No

Q

No

PG Pulses/Rev

F1-02

Operation selec-
tion at PG open
circuit (PGO)

Sets stopping method when a PG

open circuit fault (PGO) occurs.
See parameter F1-14.

0: Ramp to stop - Decelerate to

stop using the active
deceleration time.

1: Coast to stop
2: Fast - Stop - Decelerate to stop

using the deceleration time in
C1-09.

3: Alarm Only - Drive continues

operation.

0 to 3

1

No

No

A

No

A

No

PG Fdbk Loss
Sel

F1-03

Operation selec-
tion at over-
speed (OS)

Sets the stopping method when an

overspeed (OS) fault occurs. See
F1-08 and F1-09.

0: Ramp to stop - Decelerate to

stop using the active
deceleration time.

1: Coast to stop
2: Fast - Stop - Decelerate to stop

using the deceleration time in
C1-09.

3: Alarm Only - Drive continues

operation.

0 to 3

1

No

No

A

No

A

A

PG Overspeed
Sel

F1-04

Operation
Selection at
Deviation

Sets the stopping method when a
speed deviation (DEV) fault
occurs.

0: Ramp to stop (Deceleration

stop using Deceleration Time
1, C1-02.)

1: Coast to stop
2: Fast stop (Emergency stop

using the deceleration time in
C1-09.)

3: Continue operation (DEV is

displayed and operation
continued.)

0 to 3

3

No

No

A

No

A

A

PG Deviation
Sel