Speed search: b3 – Yaskawa G7 Drive User Manual

Page 126

Advertising
background image

User Parameter Tables

5-

15

„

Speed Search: b3

User parameters for the speed search are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

b3-01

Speed
Search
Selection

Enables/disables and selects

the speed search function at
start.

0: Speed Estimation Speed

Search Disable - Speed
search at start is disabled
(however the estimated
speed method is used for
multi-function input, power
loss ridethrough, auto fault
retry)

1: Speed Estimation Speed

Search Enable - The speed
estimation method of speed
search is enabled at run
command.

2: Current Detection Speed

Search Disable - Speed
search at start is disabled
(however the current
detection method is used
for multi-function input,
power loss ride through,
auto fault retry)

3: Current Detection Speed

Search Enable - The current
detection method of speed
search is enabled at run
command.

Speed Estimation Method:

Motor speed and direction are
measured using residual
motor flux.

Current Detection Method:

Motor speed is measured
using current feedback levels
(unidirectional only).

0 to 3

2

*

No

A

A

A

No

A

191H

SpdSrch at
Start

b3-02

Speed
Search
Deactivation
Current

Used only when b3-01 = 2 or
3. Sets speed search operating
current in units of percent, with
drive rated current as 100%.
Note: Normally not necessary
to change. If the drive won't
run after a restart, lower this
value.

0

to

200

100%

**

No

A

No

A

No

A

192H

SpdSrch
Current

b3-03

Speed
Search
Deceleration
Time

Used only when b3-01 = 2 or
3. Sets the deceleration time
during speed search.

0.1

to

10.0

2.0 s

No

A

No

A

No

No

193H

SpdSrch
Dec Time