Motor 2 setup: e4 – Yaskawa G7 Drive User Manual

Page 150

Advertising
background image

User Parameter Tables

5-

39

„

Motor 2 Setup: E4

User parameters for motor 2 are shown in the following table.

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

E4-01

Motor 2
Rated Current

Sets the motor 2 name plate
full load current in amperes
(A). This value is automatically
set during Auto-Tuning.

0.32

to

6.40

*2

1.90 A

*1

No

A

A

A

A

A

321H

Motor Rated
FLA

E4-02

Motor 2
Rated Slip

Sets the rated slip of motor 2
in hertz (Hz). This value is
automatically set during
rotational Auto-Tuning.

0.00

to

20.00

2.90Hz

*1

No

A

A

A

A

A

322H

Motor Rated
Slip

E4-03

Motor 2 No-
load Current

Sets the magnetizing current of
motor 2 in percentage of full
load current (E4-01). This value
is automatically set during
rotational Auto-Tuning.

0.00

to

1.89

*3

1.20 A

*1

No

A

A

A

A

A

323H

No-Load
Current

E4-04

Motor 2
Number of Poles
(number of
poles)

Sets the number of poles of
motor 2. This value is
automatically set during
Auto-Tuning.

2 to 48 4 poles

No

No

A

No

A

A

324H

Number of
Poles

E4-05

Motor 2
Line-to-line
Resistance

Sets the phase-to-phase
resistance of motor 2 in ohms.
This value is automatically
set by the Auto-Tuning.

0.000

to

65.000

9.842

Ω

*1

No

A

A

A

A

A

325H

Term
Resistance

E4-06

Motor 2 Leak
Inductance

Sets the voltage drop due to
motor leakage inductance as a
percentage of rated voltage of
motor 2. This value is
automatically set during
Auto-Tuning.

0.0

to

40.0

18.2%

*1

No

No

No

A

A

A

326H

Leak
Inductance

E4-07

Motor 2
Rated
Output

Sets the rated power of motor
2 in kilowatts (kW). This
value is automatically set
during Auto-Tuning.

0.00

to

650.00

0.40kW

*1

No

A

A

A

A

A

327H

Mtr Rated
Power

E4-08

Slip
Compensation
Gain - Motor 2

This parameter can help to
increase speed precision
when working on a load,
although normally adjustment
is not required.

- When speed is less than

that desired value,
increase the set value.

- When speed is higher than

the desired value, decrease
the set value

*This parameter functions as

gain suppression when in
flux vector mode.

0.0

to

2.5

1.0

*1

Yes

A

No

A

A

A

33EH

SlpCmp Gain
Mtr2

Advertising