Related parameters, Selecting pulse monitor items, Adjusting the pulse monitor items – Yaskawa G7 Drive User Manual

Page 299: Application precautions, Using pulse train monitor contents, Related parameters „ selecting pulse monitor items

Advertising
background image

6

-82

‹

Using Pulse Train Monitor Contents

This section explains pulse monitor parameters.

„

Related Parameters

„

Selecting Pulse Monitor Items

Output digital operator monitor items (U1-

††

[status monitor]) from pulse monitor terminal MP-AC. Refer

to Chapter 5 User Parameters, and set the

††

part of U1-

††

(Status monitor). The possible monitor selec-

tions are limited as follows: U1-01, 02, 05, 20, 24, 36.

„

Adjusting the Pulse Monitor Items

Adjust the pulse frequency output from pulse monitor terminal MP-AC. Set the pulse frequency output when
100% frequency is output to H6-07.

Set H6-06 to 2, and H6-07 to 0, to output the frequency synchronous with the Drive's U-phase output.

„

Application Precautions

When using a pulse monitor parameter, connect a peripheral device according to the following load condi-
tions. If the load conditions are different, there is a risk of characteristic insufficiency or damage to the
machinery.

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

H6-06

Terminal MP
Pulse Train
Monitor
Selection

Select the pulse train monitor output
terminal MP function (value of the
xx part of U1-xx). See Table A2 for
the list of U1 monitors.

1, 2, 5,
20, 24,

31, 36

only

2

Yes

A

A

A

A

A

Pulse Output
Sel

H6-07

Pulse Train
Monitor
Scaling

Sets the number of output pulses
when the monitor is 100% (inHz).
Set H6-06 to 2, and H6-07 to 0, to
make the pulse train monitor output
synchronous to the output
frequency.

0

to

32000

1440Hz

Yes

A

A

A

A

A

PO Scaling

Using a Sourcing Output

Output Voltage

(Isolated)

VRL (V)

Load Impedance (k

Ω)

+5V min.

1.5 k

Ω min.

+8V min.

3.5 k

Ω min.

+10V min.

10 k

Ω min.

Load impedance

MP

AC

VRL