Stall prevention: l3 – Yaskawa G7 Drive User Manual

Page 174

Advertising
background image

User Parameter Tables

5-

63

* 1. Factory settings will vary based on drive capacity (values given here are for 208-240Vac, 0.4kW).
* 2. Setting value for 208-240Vac. Double the value when working with 380-480Vac drives.
* 3. When set to zero, the motor will accelerate to the speed set acceleration time (C1-01 thru C1-08).

„

Stall Prevention: L3

User parameters for the stall prevention function are shown in the following table.

L2-06

KEB
Deceleration
Rate

Sets the time required to
decelerate to zero speed when a
KEB command is input from a
multi-function input.

0.0

to

200.0

0.0sec

No

A

A

A

A

A

48AH

KEB Decel
Time

L2-07

Momentary
Recovery
Time

Set the time (in seconds) to
accelerate to the set speed after
recovery from a momentary
power loss. If setting = 0.0,
then active acceleration time is
used instead.

0.0

to

25.5

0.0sec

*3

No

A

A

A

A

A

48BH

UV Return
Time

L2-08

Frequency
Reduction
Gain at
KEB Start

Sets the percentage of output
frequency reduction at the
beginning of deceleration when
a KEB command is input from
multi-function input.
Reduction =
(SlipFreqBeforeKEB) x L2-08
x 2

0

to

300

100%

No

A

A

A

A

A

48CH

KEB
Frequency

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

L3-01

Stall
Prevention
Selection
During
Accel

Selects the stall prevention

method used to prevent
excessive current during
acceleration.

0: Disabled - Motor

accelerates at active
acceleration rate. The motor
may stall if load is too
heavy or accel time is too
short.

1: General Purpose - When

output current exceeds

L3-02 level, acceleration

stops. Acceleration will
continue when the output
current level falls below the
L3-02 level.

2: Intelligent - The active

acceleration rate is ignored.
Acceleration is completed
in the shortest amount of
time without exceeding the
current value set in L3-02.

0 to 2

1

No

A

A

A

No

No

48FH

StallP
Accel Sel

Parameter

Number

Name

Description

Setting

Range

Factory

Setting

Change

during

Operation

Control Methods

MODBUS

Register

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2