Related parameters, Multi-function contact inputs (h1-01 to h1-10), Application precautions – Yaskawa G7 Drive User Manual

Page 294: Setting precautions

Advertising
background image

Input Terminal Functions

6-

77

„

Setting Precautions

To switch command inputs between the Communications Option Card and the control circuit terminals, set the
following parameters.

•

Set b1-01 (Reference Selection) to 1 (Control circuit terminal [analog input])

•

Set b1-02 (Operation Method Selection to 1 (Control circuit terminal (sequence inputs])

•

Set one of the parameters H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selec-
tion) to 2 (Option/Drive selection).

‹

Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)

The FJOG/RJOG command functions operate the Drive using jog frequencies by using the terminal ON/OFF
operation. When using the FJOG/RJOG commands, there is no need to input the run command.
To use this function, set one of the parameters H1-01 to H1-10 (multi-function contact input terminal S3 to
S12 function selection) to 12 (FJOG command) or 13 (RJOG command).

„

Related Parameters

*1 Setting range changes to 0 thru 66.0 when operating in Vector 2 wo/PG.. The upper limit for the setting range also depends on the upper limit in E1-

04. The max setting is 400.00.

Multi-Function Contact Inputs (H1-01 to H1-10)

„

Application Precautions

•

Jog frequencies using FJOG and RJOG commands are given priority over other frequency references.

•

When both FJOG command and RJOG commands are ON for 500ms or longer at the same time, the Drive
stops according to the setting in b1-03 (stopping method selection).

Terminal Status

Frequency Reference and Run Command Selection

OFF

Drive
(Can be operated from frequency reference or control circuit terminal from analog input termi-
nal.)

ON

Communications Option Card
(Frequency reference and run command are enabled from communications Option Card.)

Parameter

Number

Name

Description

Setting
Range

Factory

Setting

Change

during

Operation

Control Methods

Display

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

d1-17

Jog Frequency
Reference

Frequency reference when: "Jog
frequency reference" is selected
via multi-function input
terminals. "Jog frequency
reference" has priority over
"multi-step speed reference 1 to
4". Parameter d1-17 is also the
reference for the JOG key on the
Digital Operator, and the multi-
function inputs "forward jog" and
"reverse jog". Setting units are
affected by o1-03.

0.00

to

400.00

*1

6.00Hz

Yes

Q

Q

Q

Q

Q

Jog Reference

Setting

Value

Function

Control Methods

V/f

V/f

with

PG

Open

Loop

Vector

1

Flux

Vector

Open

Loop

Vector

2

12

FJOG command (ON: Forward run at jog frequency d1-17)

Yes

Yes

Yes

Yes

Yes

13

RJOG command (ON: Reverse run at jog frequency d1-17)

Yes

Yes

Yes

Yes

Yes