4.2 Modes

4 - 33

4.2.7 Autotuning Mode

CAUTION

D

Disconnect the load (machine, device) from the motor before autotuning.

The motor may turn, possibly resulting in injury or damage to equipment. Also, motor constants cannot be

correctly set with the motor attached to a load.

Autotuning automatically tunes and sets the required motor constants when operating in the open-loop or

flux vector control modes. Always perform autotuning before starting operation.
When the rated voltage, rated current, rated frequency, and number of poles listed on the motor nameplate

have been input and the RUN Key is pressed, the motor constants calculated from these values will be writ-

ten to E1-04 through E2-09 automatically.
When motor cannot be disconnected from the load, motor constants can be set by calculation.

Contact your Yaskawa representatives for details.
The autotuning mode won’t be displayed if V/f control has been selected. Refer to Setting the Control Meth-

od: A1-02 under 4.2.5 Initialize Mode.
The Inverter’s autotuning function automatically determines the motor constants, while a servo system’s

autotuning function determines the size of a load, so these autotuning functions are fundamentally different.

Autotuning Procedure

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

G5* Main Menu *

Operation

2

press 3 times.

G5* Main Menu *

Autotuning

3

DATA

ENTER

Rated Voltage (see note)

400.0 VAC

4

DATA

ENTER

Rated Voltage

400.0 VAC

The leading digit blinks.
When Increment Key is pressed, blink-

ing value increases. When Decrement

Key is pressed, blinking value de-

creases.

5

RESET

Rated Voltage

400.0 VAC

The digit to be set moves to the right

and blinks. Follow the above proce-

dures as outlined in step 4.

6

DATA

ENTER

Entry Accepted

After selecting values for steps 4 and 5,

press DATA/ENTER Key.
The Operator display is as shown on

the left. The value is written-in.

Rated Voltage

400.0 VAC

After a few seconds, the Operator dis-

play is as shown on the left.

7

Rated Current

370 A

8

RESET

DATA
ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of

rated voltage setting.

9

Rated Frequency

60.0 HZ

10

RESET

DATA

ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of

rated voltage setting.

4

A

EXAMPLE

"