Yaskawa G5HHP Drive User Manual

Page 266

Advertising
background image

Advanced Operation

7.5.7 Operator Constants: o

7 - 102

D

Settings

Setting

Function

0

DATA/ENTER Key input required.

1

DATA/ENTER Key input not required.

Operation Selection when Digital Operator is Disconnected: o2-06

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o2-06

Operation selection

when digital operator

is disconnected

x

0, 1

--

0

A

A

A

A

D

This constant specifies whether to stop operation when the Digital Operator is disconnected.

D

Settings

Setting

Function

0

Disable Operator detection. (Continue operation when the Digital Operator is disconnected.)

1

Enable Operator detection. (Detect an OPR fault when the Digital Operator is disconnected, stop

the Inverter output, and operate the fault contact.)

Cumulative Operation Time Settings: o2-07, o2-08

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o2-07

Cumulative operation

time setting

x

0 to 65535

h

0

A

A

A

A

o2-08

Cumulative operation

time selection

x

0, 1

--

0

A

A

A

A

D

Set the initial elapsed time in constant o2-07. The elapsed operating time will start from this value.

D

Constant o2-08 determines whether the elapsed operating time is the time that the Inverter is on or the

time that the Inverter is running.

D

Settings

Setting

Function

0

Inverter power-on time. (Counts the elapsed time from start-up until power is turned off.)

1

Inverter running time. (Counts the elapsed time that there is an Inverter output.)