User Constants

8.2.6 Terminal Constants: H

8 - 26

Constant

Number

Page

Control Methods

Change

during

Opera-

tion

Factory

Setting

Setting

Range

Description

Name

Constant

Number

Page

Flux

Vector

Open

Loop

Vector

V/f

with

PG

V/f

Change

during

Opera-

tion

Factory

Setting

Setting

Range

Description

Display

F6-01

Output mode selec-

tion

Effective when a DO-08 Digital

Output Card is used.
Set the output mode.

0, 1

0

x

B

B

B

B

7 - 60

F6 01

DO-08 Selection

Set the output mode.
0: 8-channel individual outputs
1: Binary code output

0, 1

0

x

B

B

B

B

7 - 60

F7-01

Frequency multiple

selection

Effective when the Pulse Monitor

Card is used.
Sets the number of output pulses.
0: 1F, 1: 6F, 2: 10F, 3: 12F, 4: 36F
;

F= the output frequency dis-

0 to 4

1

x

B

B

B

B

7 - 61

F7 01

PO-36F Selection

;

F= the output frequency dis-

played in Hz.

Example: When 0 (1F) is set, and

the output frequency is 60 Hz, 60

pulses per second are output.

(50% duty)

0 to 4

1

x

B

B

B

B

7 - 61

F8-01

Optical option (SI-

F/G)

0: Deceleration to stop
1: Coast to stop
2 Em r nc stop

0 to 3

1

f

B

B

B

B

----

F8 01

E-15 Det Sel

2: Emergency stop
3: Continue operation

0 to 3

1

f

B

B

B

B

----

F9-01

External fault input

level from Optical op-

tion

0: NO contact
1: NC contact

0, 1

0

x

B

B

B

B

----

E-15 Selection

1: NC contact

F9-02

External fault from

Optical option

0: Always detect
1: Detect during operation

0, 1

0

x

B

B

B

B

----

F9 02

EFO Detection

1: Detect during operation

0, 1

0

x

B

B

B

B

----

F9-03

Action for external

fault from Optical op-

tion

0: Deceleration to stop
1: Coast to stop
2: Emergency stop

0 to 3

1

x

B

B

B

B

----

EFO Fault Act

2: Emergency stop
3: Continue operation

F9-04

Optical option trace

sampling time

----

0 to

60000

0

x

B

B

B

B

----

F9 04

Trace Sample Time

----

60000

0

x

B

B

B

B

----

8.2.6 Terminal Constants: H

J

Multi-function Inputs: H1

C

t t

S tti

F t

Change

Control Methods

Constant

Number

Name

Display

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

H1-01

Multi-function input 1

(terminal 11)

Terminal 11 Sel

0 to 77

24

x

B

B

B

B

7 - 63

H1-02

Multi-function input 2

(terminal 12)

Terminal 12 Sel

0 to 77

14

x

B

B

B

B

7 - 63

H1-03

Multi-function input 3

(terminal 13)

Terminal 13 Sel

0 to 77

3 (0) *

x

B

B

B

B

7 - 63

H1-04

Multi-function input 4

(terminal 14)

Terminal 14 Sel

0 to 77

4 (3) *

x

B

B

B

B

7 - 63

H1-05

Multi-function input 5

(terminal 15)

Terminal 15 Sel

0 to 77

6 (4) *

x

B

B

B

B

7 - 63

H1-06

Multi-function input 6

(terminal 16)

Terminal 16 Sel

0 to 77

8 (6) *

x

B

B

B

B

7 - 63

8