Basic Operation

6.4.1 PG Speed Control Card Settings

6 - 26

6.4 Flux Vector Control

With flux vector control (vector control with PG), make the settings for the PG Speed Control Card, select the

zero-speed operation method, set the various autotuning constants, and then adjust the gain of the speed control

loop.

Always perform auto--tuning for motor unit separately before vector control operation. Vector control is not ef-

fective without autotuning.
To ensure high-accuracy torque/speed control, use a motor specifically designed for vector control with an inte-

grated PG.
When setting up a PG (encoder), connect it directly to the motor shaft. If the PG is connected to the motor via

gearing or belts, responses can be delayed by backlash or torsion; the delayed responses can generate oscillation

and make control impossible.

6.4.1 PG Speed Control Card Settings

J

Available PG Speed Control Cards

D

There are 4 models of PG Speed Control Cards, but only 2 models can be used with vector control.

PG-B2: Phase-A/Phase-B pulse inputs, complementary output

PG-X2: Phase-A/Phase-B/Phase-Z pulse inputs, line drivers

D

Select the Card according to the application and install it in the Inverter as described in 3.7 Installing

and Wiring PG Speed Control Cards.

J

PG Constant: F1-01

D

Set the PG (pulse generator or encoder) constant in pulses/revolution.

D

Set the number of phase-A or phase-B pulses in one motor revolution.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

F1-01

PG constant

x

0 to 60000

p/r

600

x

Q

x

Q

J

PG Rotation Direction: F1-05

D

This constant is used to coordinate the PG’s rotation direction with the motor’s rotation direction.

The setting for the standard applicable Yaskawa PG (made by Thermtac) is an advanced phase A for

forward rotation.

D

Generally, phase A leads when the PG rotates in the clockwise direction (looking from the input axis).

When a forward reference is output, the motor rotates in the counterclockwise direction (looking from

the output axis).

D

Set whether phase A or phase B leads when the motor operates in the forward direction.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

F1-05

PG rotation

x

0, 1

--

0

x

B

x

B

D

Settings

Setting

Function

0

Phase A leads with forward rotation. (Phase B leads with reverse rotation.)

1

Phase B leads with forward rotation. (Phase A leads with reverse rotation.)

6

Advertising