7.5 Common Functions

7 - 63

Setting

value

Control Method

Function

Setting

value

Flux

vector

Open

loop

Vector

V/f

w/

PG

V/f

Function

30

PID control integral reset (ON: Reset)

f

f

f

f

60

DC injection braking command (ON: Performs DC injection braking)

f

f

f

f

61

External speed search command 1: Maximum output frequency (ON: speed search)

f

x

f

x

62

External speed search command 2: Set frequency (ON: speed search)

f

x

x

x

63

Energy-saving command (ON: Energy-saving control set for b8-01, b8-02)

f

f

x

x

64

External speed search command 3

f

f

f

f

65

KEB (deceleration at momentary power loss) command (NO contact)

f

f

f

f

66

KEB (deceleration at momentary power loss) command (NO contact)

f

f

f

f

71

Speed/torque control change (ON: Torque control)

x

x

x

f

72

Zero-servo command (ON: Zero-servo)

x

x

x

f

77

Speed control (ASR) proportional gain switch (ON: C5-03)

x

x

x

f

Constant Settings

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H1-01

Multi-function input 1

(terminal 11)

x

0 to 77

--

24

B

B

B

B

H1-02

Multi-function input 2

(terminal 12)

x

0 to 77

--

14

B

B

B

B

H1-03

Multi-function input 3

(terminal 13)

x

0 to 77

--

3 (0)

B

B

B

B

H1-04

Multi-function input 4

(terminal 14)

x

0 to 77

--

4 (3)

B

B

B

B

H1-05

Multi-function input 5

(terminal 15)

x

0 to 77

--

6 (4)

B

B

B

B

H1-06

Multi-function input 5

(terminal 16)

x

0 to 77

--

8 (6)

B

B

B

B

D

The factory settings in parentheses are for when the Unit is initialized for 3-wire control.

D

The following table shows the settings and section references for some common functions.

Function

Setting

Section

3-wire sequence (forward/reverse run command)

0

6.1.8

Multi-step speed references 1 to 3 and jog frequen-

cy reference

3 to 6

6.1.8

Accel/Decel time 1 and 2

7, 1A

6.1.8

Emergency stop

15

6.1.8

FJOG/RJOG commands

12, 13

6.1.8

Terminal 36/39 switch

1F

6.1.8

Timer function input

18

7.5.1

Energy-saving command

63

7.2.1, 7.4.1

Local/Remote Selection (Setting: 1)

OFF

Operate with the frequency reference and run command specified in b1-01 (the frequency refer-

ence source) and b1-02 (run source).

ON

Operate with the frequency reference and run command set at the Digital Operator.

7