8.2 Programming Mode Constants

8 - 33

8.2.7 Protection Constants: L

J

Motor Overload: L1

C

t t

Name

S tti

F t

Change

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

L1-01

Motor protection

selection

Sets whether the motor overload

function is enabled or disabled at

electric thermal overload relay.
0: Disabled
1: Enabled
;

In some applications when the

Inverter power supply is turned

off, the thermal value is reset, so

0, 1

1

x

B

B

B

B

7 - 84

L1 01

MOL Fault Select

off, the thermal value is reset, so

even if this constant is set to 1,

(Enabled), protection may not be

effective.

When several motors are con-

nected to one Inverter, set to 0

(Disabled) and ensure that each

motor is installed with a protec-

tion device.

0, 1

1

x

B

B

B

B

7 - 84

L1-02

Motor protection time

constant

Sets the electric thermal detection

time in seconds units.
;

Usually setting is not necessary.

The factory setting is 150% over-

load for one minute.

0.1 to

5 0

1.0

x

B

B

B

B

7 - 84

L1 02

MOL Time Const

load for one minute.

When the motor’s overload re-

sistance is known, set at the

overload resistance when the

motor is hot started.

5.0

1.0

x

B

B

B

B

7 - 84

J

Power Loss Ridethrough: L2

C

t t

Name

S tti

F t

Change

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

L2-01

Momentary power

loss detection

0: Disabled (Undervoltage fault

detection)

1: Enabled (Restarted when the

power returns within the time

for L2-02. When L2-02 is ex-

ceeded, undervoltage fault

detection )

0 to 2

0

x

B

B

B

B

7 - 85

L2 01

PwrL Selection

detection.)

2: Enabled while CPU is operat-

ing. (Restarts when power re-

turns during control operations.

Does not detect undervoltage

fault.

0 to 2

0

x

B

B

B

B

7 - 85

L2-02

Momentary power

loss ridethru time

Sets the recovery time, when mo-

mentary power loss selection

(L2-01) is set to 1 in units of one

0.0 to

2 0

1.0

*1

x

B

B

B

B

7 - 85

L2 02

PwrL Ridethru t

(L2-01) is set to 1, in units of one

second.

2.0

*1

x

B

B

B

B

7 - 85

L2-03

Min. baseblock time

Sets the Inverter’s minimum base-

block time in units of one second,

when the Inverter is restarted after

power loss ridethrough.
;

Sets the time for the motor’s re-

0.0 to

10.0

x

B

B

B

B

7 87

L2-03

PwrL Baseblock t

;

Sets the time for the motor s re-

sidual voltage to dissipate.

When an overcurrent occurs

when starting a speed search or

DC injection braking, increase

the set values.

0.0 to

25.5

10.0

*1

x

B

B

B

B

7 - 87