2 specifications of options and peripheral devices, 1 selection of mccb and ground fault interrupter, 2 module draw-out lift – Yaskawa G5HHP Drive User Manual

Page 344: V class inverters

Advertising
background image

Specifications

11.2.1 Selection of MCCB and Ground Fault Interrupter

11 - 4

11.2 Specifications of Options and Peripheral Devices

11.2.1 Selection of MCCB and Ground Fault Interrupter

Be sure to install an MCCB or ground fault interrupter on the power supply side in order to protect the Invert-

er wirings.
When using an MCCB, use one that has the sensitivity current of 200 mA min. and operation time of 0.1 s

min. and also that incorporates countermeasures against harmonics.
The following tables show MCCB selection examples.

J

400-V Class Inverters

VS-616G5 Model

CIMR-G5Aj

Output Capacity

(kVA)

Rated Output Cur-

rent (A)

MCCB Model

Rated Current (A)

4200

320

414

NF600

600

4400

610

800

NF1200

1200

4600

910

1200

NF2000

1800

4800

1200

1600

NF2500

2500

J

575-V Class Inverters

VS-616G5 Model

CIMR-G5Aj

Output Capacity

(kVA)

Rated Output Cur-

rent (A)

MCCB Model

Rated Current (A)

5300

410

414

NF600

600

5600

800

800

NF1200

1200

5900

1200

1200

NF2000

1800

512C

1600

1600

NF2500

2500

11.2.2 Module Draw-out Lift

The following two lifts and a crane are available for drawing out the Module.

11