Setting User Constants

4.2.5 Initialize Mode

4 - 22

J

Selecting the Display Language: A1-00

D

Use constant A1-00 to select the language displayed by the Inverter. A value of 0 sets English and a value

of 1 sets Japanese.

D

This user constant is not returned to the factory setting when constants are initialized. It must be manual-

ly reset to the factory setting.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

A1-00

Language selection

for Digital Operator

display

f

0 (English),

1 (Japanese)

--

1

(Japanese)

Q

Q

Q

Q

Changing the Language to English

Use the following procedure to change the display language from Japanese to English.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

2

3

DATA

ENTER

4

DATA

ENTER

Changed to constant setting level.

5

A1--00 = 0

English

6

DATA

ENTER

Entry Accepted

Writes-in the new setting.

Select Language

English

After a few seconds, the Operator dis-

play is as shown on the left.

The display language has been set to English.

J

Setting the Access Level: A1-01

D

Use constant A1-01 to select the user constant access level. This level determines which user constants

can be changed and displayed.

D

The user constants that can be displayed and changed also depend upon the control method being used.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

A1-01

Constant access level

f

0 to 4

--

2 (Q)

Q

Q

Q

Q

Access Level Settings

Setting

Function

0

Operation Only

This setting allows the operation mode and initialize mode to be changed or

displayed.
Use this setting to prevent user constant settings from being changed.

1

User Program

This setting allows only the user-selected constants (up to 32) to be changed or

displayed.
Select the desired user constants in A2-01 through A2-32.

2

Quick-start

This setting allows the user constants required to start the Inverter (about 25)

to be changed or displayed.

4

A

EXAMPLE

"