Setting User Constants
4.2.5 Initialize Mode
4 - 22
J
Selecting the Display Language: A1-00
D
Use constant A1-00 to select the language displayed by the Inverter. A value of 0 sets English and a value
of 1 sets Japanese.
D
This user constant is not returned to the factory setting when constants are initialized. It must be manual-
ly reset to the factory setting.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
A1-00
Language selection
for Digital Operator
display
f
0 (English),
1 (Japanese)
--
1
(Japanese)
Q
Q
Q
Q
Changing the Language to English
Use the following procedure to change the display language from Japanese to English.
Step
Key Sequence
Digital Operator Display
Remarks
1
MENU
2
3
DATA
ENTER
4
DATA
ENTER
Changed to constant setting level.
5
A1--00 = 0
English
6
DATA
ENTER
Entry Accepted
Writes-in the new setting.
Select Language
English
After a few seconds, the Operator dis-
play is as shown on the left.
The display language has been set to English.
J
Setting the Access Level: A1-01
D
Use constant A1-01 to select the user constant access level. This level determines which user constants
can be changed and displayed.
D
The user constants that can be displayed and changed also depend upon the control method being used.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
A1-01
Constant access level
f
0 to 4
--
2 (Q)
Q
Q
Q
Q
Access Level Settings
Setting
Function
0
Operation Only
This setting allows the operation mode and initialize mode to be changed or
displayed.
Use this setting to prevent user constant settings from being changed.
1
User Program
This setting allows only the user-selected constants (up to 32) to be changed or
displayed.
Select the desired user constants in A2-01 through A2-32.
2
Quick-start
This setting allows the user constants required to start the Inverter (about 25)
to be changed or displayed.
4
A
EXAMPLE
"