9.1 Protective and Diagnostic Functions

9 - 3

Corrective Actions

Probable Causes

Meaning

Fault Display

UV3

MC Answerback

Inrush Prevention Circuit Fault
A fault occurred in the inrush preven-

tion circuit.

----

S

Try turning the power supply off and

on.

S

Replace the Inverter if the fault con-

tinues to occur.

PF

Input Pha Loss

Main Circuit Voltage Fault
The main circuit DC voltage oscillates

unusually (not when regenerating).
This fault is detected when L8-05 is

set to “Enabled.”

S

An open-phase occurred in the input

power supply.

S

A momentary power loss occurred.

S

The wiring terminals for the input

power supply are loose.

S

The voltage fluctuations in the input

power supply are too large.

S

The voltage balance between phases

is bad.

Reset the fault after correcting its

cause.

LF

Output Pha Loss

Output Open-phase
An open-phase occurred at the Invert-

er output.
This fault is detected when L8-07 is

set to “Enabled.”

S

There is a broken wire in the output

cable.

S

There is a broken wire in the motor

winding.

S

The output terminals are loose.

Reset the fault after correcting its

cause.

Output Pha Loss

The motor being used has a capacity

less than 5% of the Inverter’s maxi-

mum motor capacity.

Check the motor and Inverter capacity.

Cooling Fin Overheating

The ambient temperature is too high.

Install a cooling unit.

OH OH1

H

i k O

The temperature of the Inverter’s

cooling fins exceeded the setting in

There is a heat source nearby.

Remove the heat source.

Heatsink Over tmp

cooling fins exceeded the setting in

L8-02 or 105°C.

The Inverter’s cooling fan has

stopped.

Replace the cooling fan. (Contact your

Inverter internal cooling fan

stopped

Inverter internal cooling fan has

stopped.

Replace the cooling fan. (Contact your

Yaskawa representative.)

RH

Dyn Brk Resistor

Installed Braking Resistor Over-

heating
The braking resistor is overheated and

the protection function set with L8-01

has operated.

The deceleration time is too short and

the regenerative energy from the mo-

tor is too large.

S

Reduce the load, increase the decel-

eration time, or reduce the motor

speed.

S

Change to a Braking Resistor Unit.

RR

Dyn Brk Transistr

Internal Braking Transistor Fault
The braking transistor is not operating

properly.

----

S

Try turning the power supply off and

on.

S

Replace the Inverter if the fault con-

tinues to occur.

OL1

Motor Overload
The motor overload protection func-

tion has operated based on the internal

l

i h

l

l

The load is too heavy. The accelera-

tion time, deceleration time, and cycle

time are too short.

Check the size of the load and the

length of the acceleration, decelera-

tion, and cycle times.

OL1

Motor Overloaded

tion has operated based on the internal

electronic thermal value.

The V/f characteristics voltage is too

high.

Check the V/f characteristics.

The motor’s rated current setting

(E2-01) is incorrect.

Check the motor’s rated current set-

ting (E2-01).

OL2

Inverter Overload
The Inverter overload protection func-

tion has operated based on the internal

l

i h

l

l

The load is too heavy. The accelera-

tion time, deceleration time and cycle

time are too short.

Check the size of the load and the

length of the acceleration, decelera-

tion, and cycle times.

OL2

Inv Overloaded

tion has operated based on the internal

electronic thermal value.

The V/f characteristics voltage is too

high.

Check the V/f characteristics.

The Inverter capacity is too low.

Replace the Inverter with one that has

a larger capacity.

OL3

Overtorque Det 1

Overtorque 1
There has been a current greater than

the setting in L6-02 for longer than

the setting in L6-03.

----

S

Make sure that the settings in L6-02

and L6-03 are appropriate.

S

Check the mechanical system and

correct the cause of the overtorque.

OL4

Overtorque det 2

Overtorque 2
There has been a current greater than

the setting in L6-05 for longer than

the setting in L6-06.

----

S

Make sure that the current setting in

L6-05 and time setting in L6-06 are

appropriate.

S

Check the mechanical system and

correct the cause of the overtorque.

9