Yaskawa G5HHP Drive User Manual

Page 215

Advertising
background image

7.5 Common Functions

7 - 51

When “1.0” is set, this function compensates for the rated slip that has been set, by the rated torque

output.

With flux vector control, this becomes the gain to compensate for slip caused by motor temperature

variation. (Refer to Slip Compensation Gain: C3-01 under 7.3.6.)

Motor Slip Compensation Gain Adjustment Procedure

1. Correctly set the motor rated slip (constant E2-02) and the motor no-load current (constant E2-03).

The motor rated slip can be calculated by means of the following equation, using the numbers that

are shown on the motor nameplate.
Motor rated slip =

Motor rated frequency (Hz) -- rated speed (r/min) x motor (No. of poles) / 120

Set the values at the rated voltage and rated frequency for the motor no-load current. With vector

control, the motor rated slip is automatically set by autotuning.

2. Set the slip compensation gain (constant C3-01 to “1.0.” (If it is set to “0.0,” slip compensation will be

disabled.)

3. Operate with a load, measure the speed, and adjust the slip compensation gain (in increments of 0.1).

If the speed is lower than the target value, increase the slip compensation gain.

If the speed is higher than the target value, decrease the slip compensation gain.

Slip Compensation Primary Delay Time: C3-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C3-02

Slip compensation

primary delay time

x

0 to 10000

ms

200 *

A

x

A

x

* When the control method is switched, the values change as follows:

V/f control: 2,000; open-loop vector: 200

D

This constant does not normally need to be set. Adjust the slip compensation primary delay time if the

motor slip compensation responsiveness is low, or if the speeds are unstable.

If responsiveness is low, lower the setting.

If speeds are unstable, raise the setting.

Slip Compensation Limit: C3-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C3-03

Slip compensation

limit

x

0 to 250

%

200

A

x

A

x

D

Constant C3-03 sets the slip compensation limit as a percentage of motor rated slip (E2-02), with the

motor rated slip taken as 100%.

D

If the speed is lower than the target value and does not change even when the slip compensation gain

is adjusted, it is possible that the slip compensation limit has been reached. Raise the limit and then check

again. Make sure, however, that the value of the sum of the reference frequency and the slip compensa-

tion limit does not exceed the speed capacity of the machinery.

D

The limit is as shown in Figure 7.25 in the constant torque and constant output areas.

Slip compensation limit

C3-03

E1-06

E1-04

Output frequency

E1-04

E1-06 ×

C3-03

E1-06: Base frequency

E1-04: Maximum output frequency

Fig 7.25

Slip Compensation Limit

7

Advertising