Frequency reference source: b1-01 – Yaskawa G5HHP Drive User Manual

Page 125

Advertising
background image

6.1 Common Settings

6 - 7

Analog Input Filter Time Constant: H3-12

D

A primary delay digital filter can be set for all three analog inputs (frequency reference (voltage), fre-

quency reference (current), and multi-function analog input)

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-12

Analog input filter

time constant

x

0.00 to 2.00

s

0.00

A

A

A

A

D

This setting is effective when there are sudden changes or noise in the analog input signal.

D

Responsiveness decreases as the setting increases.

6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09

J

Frequency Reference Source: b1-01

D

Select the reference source.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b1-01

Reference selection

x

0 to 3

--

1

Q

Q

Q

Q

D

Settings

Setting

Reference source

0

Digital Operator

1

Control circuit terminals (analog inputs)

2

Transmission

3

Optional Card

D

The frequency reference is input from the Digital Operator, so set b1-01 to 0.

J

Frequency Unit for Reference Setting and Monitoring: o1-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o1-03

Frequency unit for

reference setting and

monitor

x

0 to 39999

--

0

B

B

B

B

D

Settings

Setting

Function

0

0.01 Hz units

1

0.01% units (The maximum frequency is 100%.)

2 to 39

r/min units (Set the number of poles.)
r/min = 120 X frequency reference (Hz)/o1--03
(o1--03 sets the motor poles.)

40 to 39999

Decimal point is set according to the 5th digit value of o1--03.
5th digit = 0: Displays
5th digit = 1: Displays

.

5th digit = 2: Displays

.

5th digit = 3: Displays .
Setting values of 100% frequency are set according to the first to fourth digits of o1--03
[Example 1]
When the setting value (100% speed) is 200.0, o1--03 is set to 12000.
When o1--03 is set to 12000, 100% speed displays 200.0. 60% speed displays 120.0.
[Example 2]
When the setting value (100% speed) is 65.00, o1--03 is set to 26500.
When o1--03 is set to 26500, 60% speed displays 39.00.

6