Trial Operation

5.2.1 Power ON

5 - 4

5.2 Trial Operation Procedures

5.2.1 Power ON

J

Checkpoints before Turning ON the Power Supply

D

Check that the power supply is of the correct voltage.

400-V class: 3-phase 380 to 460 VAC, 50/60 Hz
575-V class: 3-phase 500 to 600 VAC, 50/60 Hz

D

Make sure that the control power matches with the control power voltage jumper.

D

Make sure that the motor output terminals (U, V, W) and the motor are connected correctly.

D

Make sure that the Inverter control circuit terminal and the control device are wired correctly.

D

Set all Inverter control circuit terminals to OFF.

D

When using a PG Speed Control Card, make sure that it is wired correctly.

D

Make sure that the motor is not connected to the mechanical system (no-load status)

5.2.2 Checking the Display Status

If the Digital Operator’s display at the time the power is connected is normal, it will read as follows:

Frequency Ref

U1--01 = 0.00 HZ

[Normal]

The frequency reference monitor is

displayed in the data display section.

When an fault has occurred, the details of the fault will be displayed instead of the above display. In that

case, refer to Chapter 9 Maintenance Operations. The following display is an example of a fault display.

UV

Under Voltage

[Fault]

The display will differ depending

on the type of fault.

5.2.3 Initializing Constants

D

When replacing the controller PCB, check the Inverter capacity (kVA) in o2-04 first and then initialize

constants to the factory settings. There is no need to initialize constants the first time trial operation is

performed after purchasing the Inverter.

D

To initialize the constants, set “2220” in A1-03 (Initialize).

D

After initialization, the access level is set to Quick-start (A1-01). The following table shows the setting

method for Quick-start.

Use the following procedure to initialize constants.

Step

Key Sequence

Digital Operator Display

Remarks

Frequency Ref

U1--01 = 0.00 HZ

1

MENU

G5* Main Menu*

Operation

Displays operation mode.

2

G5* Main Menu*

Initialize

Displays initialize mode.

3

DATA

ENTER

Select Language

English

Puts the Inverter in initialize mode.

4

Press 3 times.

Initialize

Select

Displays the Initialize display.

5

DATA

ENTER

A1-03 = 0***

Select

Displays the constant setting for A1-03.

6

A1-03 = 2220

2--wire Initial

Initializes for a 2-wire sequence.

5