11.1 Standard Inverter Specifications

11 - 3

575-V Class Inverters

400-V Class Inverters

Model number

CIMR-G5A

512C8

59008

56008

53008

48008

46008

44008

42008

Model number

CIMR-G5A

Motor protection

Protection by electronic thermal overload relay.

Instantaneous over-

current protection

Stops at approx. 200% of rated output current.

Fuse blown protec-

tion

Stops for fuse blown.

Overload protection

Stops in one minute at approx. 150% of rated output current.

cti

ons

Main circuit overvol-

tage protection

Stops when main-circuit DC voltage is approx. 820 V.

Stops when main-circuit DC voltage is approx. 1040 V.

ve

func

t

Main circuit undervol-

tage protection

Stops when main-circuit DC voltage is approx. 380 V.

Stops when main-circuit DC voltage is approx. 480 V.

rotec

tiv

e

Momentary power

loss ridethru

Stops for 15 ms or more. By selecting the momentary power loss mode, operation can be continued if power is restored within 2 s.

Pr

o

Cooling fin overheat-

ing

Protection by thermistor.

Stall prevention

Stall prevention during acceleration, deceleration, or running.

Grounding protection

Protection by electronic circuits. (Overcurrent level)

Charge indicator (in-

ternal LED)

Lit when the main circuit DC voltage is approx. 50 V or more.

Ambient operating

temperature

--10° to 40°C

m

ent

Ambient operating

humidity

90 % RH max. (no condensing)

ronm

e

Storage temperature

--20°C to +60°C

E

nvi

ro

Application site

Indoor (no corrosive gas, dust, etc.)

E

Altitude

1000 m max.

Vibration

2 m/s

2

(0.2G) max

Note 1. Autotuning is sometimes required.

2. Operate in the flux vector control or open-loop vector control mode. Operation in the V/f control mode should be avoided.