Advanced Operation

7.5.5 External Terminal Functions: H

7 - 64

D

With this setting, the multi-function input selects the input method for the frequency reference and run

command.

D

The input method can be switched only when the Inverter is stopped.

D

The Digital Operator LOCAL/REMOTE Key is disabled when this function has been set in a multi-

function input.

Option Card/Inverter Selection (Setting: 2)

OFF

The Inverter frequency reference is enabled.

ON

The Option Card frequency reference is enabled.

D

With this setting, the multi-function input enables the frequency reference input from the Inverter itself

or the one from Option Card. The frequency reference input can be switched only when the Inverter is

stopped.

D

Be sure that b1-01 (the frequency reference source selector) has been set to 0 (Operator) or 1 (external

terminal). Only the frequency reference from the Option Card will be enabled if b1-01 is set to 3 (Option

PCB).

D

Setting 2 can’t be selected if the AI-14B is being used and constant F2-01 (AI-14 Input Selector) is set

to 0.

External Baseblock NO (Setting: 8)

OFF

Normal operation

ON

Baseblock

External Baseblock NC (Setting: 9)

OFF

Baseblock

ON

Normal operation

D

With either of these settings, the multi-function input controls baseblock operation.

D

Baseblock is an interruption of the Inverter output. The motor coasts while the baseblock command is

being input.

D

The output frequency is retained internally, so the same frequency will be output again when the base-

block command is cleared. The output frequency will change in a step pattern when the output resumes,

so take some safety precaution such as turning OFF the run command -- especially if the baseblock com-

mand was input when the motor was operating at high speed. (When the run command is turned OFF,

the internally retained output frequency is reset to zero.)

D

After a baseblock command is cleared, the voltage will be restored in the voltage recovery time set in

L2-04.

Run/stop command

OFF

ON

Baseblock command

Input

Cleared

Frequency reference

Output frequency

The retained output frequency

is output in a step pattern.

Coasting

Fig 7.30

Baseblock Command

Acceleration/Deceleration Ramp Hold (Setting: A)

OFF

Normal operation or restart acceleration/deceleration.

ON

Pause acceleration/deceleration and maintain the present frequency.

7