V class inverters – Yaskawa G5HHP Drive User Manual

Page 308

Advertising
background image

User Constants

8.2.10 Factory Settings that Change with the Inverter Capacity (o2-04)

8 - 42

8.2.10 Factory Settings that Change with the Inverter Capacity (o2-04)

J

400-V Class Inverters

Con-

stant

No.

Name

Unit

Factory Setting

--

Inverter Capacity

kW

200

400

600

800

o2-04

kVA selection

1

81

82

83

84

C6-01

Carrier frequency upper limit

kHz

2.0

2.0

2.0

2.0

--

Carrier frequency upper limit

range

kHz

2.0

2.0

2.0

2.0

C6-02

Carrier frequency lower limit

kHz

2.0

2.0

2.0

2.0

C6-03

Carrier frequency proportional

gain

1

0

0

0

0

E2-01

(E5-01)

Motor rated current

A

370.0

740.0

1110.0

1480.0

E2-02

(E5-02)

Motor rated slip

Hz

1.30

1.30

1.30

1.30

E2-03

(E5-03)

Motor no-load current

A

96.0

192.0

288.0

384.0

E2-05

(E5-05)

Motor line-to-line resistance

0.020

0.010

0.005

0.002

E2-06

(E5-06)

Motor leak inductance

%

5.0

5.0

5.0

5.0

L2-02

Momentary power loss ridethru

time

sec

1.0

1.0

1.0

1.0

L2-03

Min. baseblock time

sec

10.0

10.0

10.0

10.0

8