Yaskawa G5HHP Drive User Manual

Page 365

Advertising
background image

12.7 User Constants

12 - 17

Table 12.1 User Constants (Continued)

No.

Name

(Display)

Factory

Setting

Setting

No.

Name

(Display)

Factory

Setting

Setting

H4-01

Monitor selection (terminal 45)

(Terminal 45 Sel)

2

L5-01

Number of auto restart attempts

(Num of Restarts)

0

H4-02

Gain (terminal 45)

(Terminal 45 Gain)

1.00

L5-02

Auto restart operation selection

(Restart Sel)

0

H4-03

Bias (terminal 45)

(Terminal 45 Bias)

0.0

L6-01

Torque detection selection 1

(Torq Det 1 Sel)

0

H4-04

Monitor selection (terminal 48)

(Terminal 48 Sel)

3

L6-02

Torque detection level 1

(Torq Det 1 Lvl)

150

H4-05

Gain (terminal 48)

(Terminal 48 Gain)

0.50

L6-03

Torque detection time 1

(Torq Det 1 Time)

0.1

H4-06

Bias (terminal 48)

(Terminal 48 Bias)

0.0

L6-04

Torque detection selection 2

(Torq Det 2 Lvl)

0

H4-07

Analog output signal level selection

(AO Level Select)

0

L6-05

Torque detection level 2

(Torq Det 2 Lvl)

150

H5-01

Station address

(Serial Comm Adr)

1F

L6-06

Torque detection time 2

(Torq Det 2 time)

0.1

H5-02

Communication speed selection

(Serial Baud Rate)

3

L7-01

Forward torque limit

(Torq Limit Fwd)

200

H5-03

Communication parity selection

(Serial Com Sel)

0

L7-02

Reverse torque limit

(Torq Limit Rev)

200

H5-04

Stopping method after communication error

(Serial Fault Sel)

3

L7-03

Forward regenerative torque limit

(Torq Lmt Fwd Rgn)

200

H5-05

Communication error detection selection

*

1

(Serial Flt Dtct)

1

L7-04

Reverse regenerative torque limit

(Torq Lmt Rev Rgn)

200

L1-01

Motor protection selection

(MOL Fault Select)

1

L8-01

Protect selection for internal DB resistor

(DB Resistor Prot)

0

L1-02

Motor protection time constant

(MOL Time Const)

1.0

L8-02

Overheat pre-alarm level

(OH Pre-Alarm Lvl)

95

L2-01

Momentary power loss detection

(PwrL Selection)

0

L8-03

Operation selection after overheat pre-alarm

(OH Pre-Alarm Sel)

3

L2-02

Momentary power loss ridethru time

(PwrL Ridethru t)

1.0

*

2

L8-05

Input open-phase protection selection

(Ph Loss In Sel)

0

L2-03

Min. baseblock time

(PwrL Baseblock t)

10.0

*

2

L8-07

Output open-phase protection selection

(Ph Loss Out Sel)

0

L2-04

Voltage recovery time

(PwrL V/F Ramp t)

0.3

*

2

o1-01

Monitor selection

(Monitor Select)

6

L2-05

Undervoltage detection level

(PUV Det Level)

380

*

3

o1-02

Monitor selection after power up

(Power-On Monitor)

1

L2-06

KEB deceleration rate

(KEB Frequency)

0.0

o1-03

Frequency units of reference setting/monitor

(Display Scaling)

0

L3-01

Stall prevention selection during accel

(StallP Accel Sel)

1

o1-04

Frequency units of constant setting

(Display Units)

0

L3-02

Stall prevention level during accel

(StallP Accel Lvl)

150

o1-05

Constant no. display selection

(Address Display)

0

L3-03

Stall prevention limit during accel

(StallP CHP Lvl)

50

o2-01

LOCAL/REMOTE key enable/disable

(Local/Remote Key)

1

L3-04

Stall prevention selection during decel

(StallP Decel Sel)

1

o2-02

STOP key during control circuit terminal opera-

tion

(Oper STOP Key)

1

L3-05

Stall prevention selection during running

(StallP Run Sel)

1

o2-03

User constant initial value

(User Defaults)

0

L3-06

Stall prevention level during running

(StallP Run Level)

160

o2-04

kVA selection

(Inverter Model #)

81

*

2

L4-01

Speed agree detection level

(Spd Agree Level)

0.0

o2-05

Frequency reference setting method

*

1

(Operator M.O.P.)

0

12

Advertising