6.3 V/f Control

6 - 21

6.3 V/f Control

With V/f control, the user must set the Inverter input voltage, motor selection, rated current, and V/f pattern.

6.3.1 Setting the Motor Constants: E1-01, E1-02, E2-01

J

Inverter Input Voltage: E1-01

D

Set the Inverter input voltage (E1-01) to match the power supply voltage.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-01

Input voltage setting

x

360 to 460

(460 to 690) VAC

400

(600)

Q

Q

Q

Q

D

The voltage settings shown in parentheses are for 575-V class Inverters.

D

This setting is used as a reference value for functions such as the protection functions.

J

Motor Selection and Rated Current: E1-02, E2-01

Motor Selection (Motor Overheating Protection: E1-02

D

Set the type of motor being used. This setting is a reference for overheating protection functions.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-02

Motor selection (mo-

tor overheating

protection)

x

0, 1

--

0

Q

Q

Q

Q

D

Settings

Setting

Function

0

Standard motor (general-purpose motor)

1

Special motor (inverter-exclusive motor)

Motor Rated Current (Electronic Thermal Reference Current): E2-01

D

Set the rated current (A) shown on the motor nameplate.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E2-01

Motor rated current

(electronic thermal

reference current)

x

10% to 200%

(of rated

current)

*1

A

*2

Q

Q

Q

Q

* 1. The setting range is 10) to 200% of the Inverter rated output current.
* 2. The factory setting depends upon the Inverter capacity. Refer to pages 8 - 42.