Advanced Operation

7.5.6 Protective Functions: L

7 - 86

Setting

Function

0

Disabled. (An undervoltage fault is detected when there is a momentary power loss.)

1

Enabled. (Restarts if power is restored within the L2-02 time. An under-voltage fault is detected

for a longer power loss.)

2

Enabled during CPU operation. (Restarts if power is restored while the CPU is operating. An

undervoltage fault is not detected.)

D

This constant specifies the processing that is performed when a momentary power loss occurs.

D

When power loss ridethru is enabled (setting 1 or 2), operation will be restarted after a speed search if

the power is restored within the allowed time interval.

D

When power loss ridethru is disabled (setting 0), an undervoltage fault will be detected if power is inter-

rupted for more than 15 ms.

Momentary Power Loss Ridethru Time: L2-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L2-02

Momentary power

loss ridethru time

x

0.0 to 2.0

s

1.0

B

B

B

B

D

The factory setting depends on the Inverter capacity. The factory setting shown in the table is for a 400-V

class, 200 kW Inverter. (See page 8 - 42.)

D

This setting is valid only when constant L2-01 is set to 1. Set the power loss ridethru time in seconds.