Yaskawa G5HHP Drive User Manual

Page 79

Advertising
background image

4.2 Modes

4 - 11

Setting a User Constant in the Advanced Access Level

The group level will be displayed when the DATA/ENTER Key is pressed at the programming mode display.
Use the following procedure to set a constant.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

G5* Main Menu *

Operation

2

Press twice.

G5* Main Menu *

Programming

3

DATA

ENTER

Group b

Application

4

Group C

Tuning

5

DATA

ENTER

Function C1

Accel/Decel

Changed to constant reading (function)

level.

6

DATA

ENTER

Accel Time 1

C1--01 = 10.0 Sec

7

DATA

ENTER

Accel Time 1

0010.0 Sec

Selects the user constant so that the

leading 0 blinks. The blinking digit can

be changed.

8

RESET

Press twice.

Accel Time 1

0010.0 Sec

Blinking digit moves 2 places to the

right and the “1” blinks.

9

Accel Time 1

0020.0 Sec

Changes 1 to 2.

10

DATA

ENTER

Entry Accepted

Writes-in the new setting, 20.0 s.

Accel Time 1

C1--01 = 20.0 Sec

After a few seconds, the Operator dis-

play is as shown on the left.

11

ESC

Function C1

Accel/Decel

The constant setting in Advanced level (acceleration time change from 10.0 to 20.0 s) has been completed.

4

A

EXAMPLE

"

Advertising