Yaskawa G5HHP Drive User Manual

Page 185

Advertising
background image

7.3 Flux Vector Control

7 - 21

D

When supplying a voltage input to the frequency reference current input (terminal 39) (a setting of 0

or 1), be sure to disconnect jumper wire J1 on the control board. (See Figure 7.10.) If the jumper wire

isn’t disconnected, the input resistor will be destroyed.

TB3

1CN

9CN

10CN

TB2

L1

J1

Jumper wire

Fig 7.10

Jumper Wire Mounting Location on Control Board

J

Speed Limit Function Settings: d5-03, H3-01, d5-04, d5-05

D

This setting selects the speed limit function used when torque control is performed.

With torque control, the motor sometimes rotates at high speed with no load or a light load. The speed

limit function keeps the motor speed from exceeding the specified limit in these cases.

D

If the speed limit is exceeded during torque control operation, a suppressing torque (proportional to the

divergence from the speed limit) is added to the torque reference. (The suppressing torque is applied

opposite to the motor rotation.)

D

There are two ways to set the motor speed limit: a constant setting or an analog input value.

Speed Limit Selection: d5-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

d5-03

Speed limit selection

x

1, 2

--

1

x

x

x

A

D

Settings

Setting

Function

1

The speed limit is set from one of the analog frequency reference terminals (36 or 39).

2

The speed limit is set to the value in constant d5-04.

Speed Limit Selection Settings: d5-03, H3-01, d5-04

D

Limit with Analog Input (d5-03 = 1)

The speed limit value is set by the input voltage (H3-01) to frequency reference (voltage) terminal

36.

When frequency reference (current) terminal 39 has been set to frequency reference by setting

constant H3-09 to 1F, this terminal is also used as an input terminal for the speed limit.

In this case, the actual speed limit value is the sum of the voltage input value at terminal 13 and the

current input value at terminal 39.

The polarity of the speed limit signal and the direction of the run command determine the direction

in which the speed is limited.

+Voltage input: Forward rotation; Speed is limited in the forward direction.

Reverse rotation; Speed is limited in the reverse direction.

--Voltage input: Forward rotation; Speed is limited in the reverse direction.

Reverse rotation; Speed is limited in the forward direction.

The speed limit value is zero for rotation opposite to the speed limit direction.

For example, when a +voltage is being input and the forward rotation command is ON, the effective

range of the torque control is from zero to the speed limit value in the forward direction (when

constant d5-05, the speed limit bias, is set to 0).

7

Advertising