Yaskawa G5HHP Drive User Manual

Page 94

Advertising
background image

Setting User Constants

4.2.5 Initialize Mode

4 - 26

The default settings of the multi-function inputs are different from the default settings of the 2-wire se-

quence.
When setting a 3-wire sequence, the operation can be started and stopped with an automatically resetting

pushbutton switch.

1

2

11

Stop switch (NC)

Run switch (NO)

5

Run command

(Operates when the run switch is closed.)

Stop command

(Stops when the stop switch is open.)

Forward/Reverse run command

(Multi-function input 3)

Sequential input common

Fig 4.9

Example of Wiring for 3-wire Sequential Operation

Initializing for 2-wire Sequential Operation

Use the following procedure to initialize user constants to the factory settings.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

G5* Main Menu *

Operation

2

G5* Main Menu *

Initialize

3

DATA

ENTER

Select Language

English

4

Press 3 times.

Init Parameters

No Initialize

5

DATA

ENTER

A1--03 = 0***

No Initialize

6

A1--03 = 2220

2-wire Initial

7

DATA

ENTER

Entry Accepted

Writes-in the new setting.

Init Parameters

No Initialize

After a few seconds, the Operator dis-

play is as shown on the left.

The initialization has been completed for a 2-wire sequence.

4

A

EXAMPLE

"