6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09

6 - 8

D

When the 40 to 39,999 range is used, any unit can be set for the reference frequency.

For example, the frequency reference can be displayed or set in units such as mm/s or m/min to coincide

with the linear operating speed of the machine.

J

Preset Frequency Reference Values: d1-01 through d1-09

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

d1-01

Frequency reference

1

f

0 to 150.00

o1-03 0.00 Hz

Q

Q

Q

Q

d1-02

Frequency reference

2

f

0 to 150.00

o1-03 0.00 Hz

Q

Q

Q

Q

d1-03

Frequency reference

3

f

0 to 150.00

o1-03 0.00 Hz

Q

Q

Q

Q

d1-04

Frequency reference

4

f

0 to 150.00

o1-03 0.00 Hz

Q

Q

Q

Q

d1-05

Frequency reference

5

f

0 to 150.00

o1-03 0.00 Hz

B

B

B

B

d1-06

Frequency reference

6

f

0 to 150.00

o1-03 0.00 Hz

B

B

B

B

d1-07

Frequency reference

7

f

0 to 150.00

o1-03 0.00 Hz

B

B

B

B

d1-08

Frequency reference

8

f

0 to 150.00

o1-03 0.00 Hz

B

B

B

B

d1-09

Jog frequency refer-

ence

f

0 to 150.00

o1-03 6.00 Hz

Q

Q

Q

Q

D

The units for these values are set in o1-03.

D

The frequency reference default value and set value will change when o1-03 is changed.

For example, if preset reference 1 is set to 6.00 Hz and o1-03 is changed to 1 (0.01% units), the setting

for preset reference 1 will become 10.00%.

D

When using preset references 2 through 8, be sure to set multi-step speed references 1, 2, and 3 in the

multi-function inputs (H1-01 through H1-06) as required.

D

When using the jog function, set the jog frequency reference in constant d1-09. When jogging from an

external terminal, set the multi-function inputs (H1-01 through H1-06) to “Jog Frequency Reference,”

“Forward Jog,” or “Reverse Jog” as required.

D

The multi-function input setting is unnecessary when jogging from the Operator.

6