Advanced Operation

7.3.6 Setting/Adjusting Motor Constants

7 - 30

Frequency (Hz)

Output voltage (V)

VMAX

(E1-05)

FMIN

(E1-09)

FA

(E1-06)

FMAX

(E1-04)

V BASE

(E1-13)

Fig 7.16

V/f Pattern Adjustment

Units for V/f Pattern Settings: o1-04

The units used for V/f pattern frequency settings can be changed when flux vector control has been selected.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o1-04

Frequency units of

constant setting

x

0, 1

--

0

x

x

x

B

D

Display Unit Settings

Setting

Function

0

Units: Hz

1

Units: r/min

D

The setting units for constants E1-04, E1-06, and E1-09 can be changed.

D

The unit for other frequencies will not change.

D

Constant o1-04 is specific to flux vector control.

J

Setting Motor Constants: E2-01 to E2-09

The motor constants (function E2) will all be set automatically when autotuning is performed.
Set these constants manually if autotuning can’t be completed properly.

Motor Rated Current: E2-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E2-01

Motor rated current

x

37.0 to

740.0

A

370

Q

Q

Q

Q

D

The setting range is 10% to 200% of the Inverter rated output current. The default setting depends upon

the Inverter capacity. (The table shows the default setting for 400-V class, 200 kW Inverters.) See page

8 - 42.)

D

Set the rated current (A) shown on the motor nameplate.

Motor Rated Slip: E2-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E2-02

Motor rated slip

x

0.00 to

20.00

Hz

1.3

A

A

Q

Q

D

The default setting depends upon the Inverter capacity.

(The table shows the default settings for 400-V class, 200 kW Inverters.) (See page 8 - 42.)

D

Calculate the rated slip (E2-02) from the value shown on the motor nameplate with the following equa-

tion and set this value.

Rated slip = rated frequency (Hz) -- rated speed (r/min) × number of poles/120

7