Emergency stop: “15, Forward and reverse jog commands: “12” and “13 – Yaskawa G5HHP Drive User Manual

Page 135

Advertising
background image

6.1 Common Settings

6 - 17

J

Acceleration/Deceleration Time Selectors 1 and 2: “7” and “1A”

D

Four acceleration times and four deceleration times can be set. The multi-function inputs can be set as

acceleration/deceleration time selectors 1 and 2 to switch between these acceleration and deceleration

times.

Setting

Function

7

Acceleration/Deceleration time selector 1

1A

Acceleration/Deceleration time selector 2

D

The following table shows which acceleration and deceleration times are selected by each possible com-

bination of acceleration/deceleration time selectors 1 and 2. The acceleration and deceleration times can

be changed while the Inverter is operating.

Accel/Decel Time Se-

lector 1

Accel/Decel Time Selec-

tor 2

Acceleration Time

Deceleration Time

OFF or not set

OFF or not set

Acceleration time 1

(C1-01)

Deceleration time 1

(C1-02)

ON

OFF or not set

Acceleration time 2

(C1-03)

Deceleration time 2

(C1-04)

OFF or not set

ON

Acceleration time 3

(C1-05)

Deceleration time 3

(C1-06)

ON

ON

Acceleration time 4

(C1-07)

Deceleration time 4

(C1-08)

J

Emergency Stop: “15”

D

When the multi-function input that is set as an emergency stop is turned ON, the motor will decelerate

to a stop at the rate set with the deceleration time in C1-09 (emergency stop time).

D

To clear the emergency stop, turn OFF the run command, turn OFF the emergency stop input, and then

turn ON the run command again.

J

Forward and Reverse Jog Commands: “12” and “13”

The jogging can be performed in forward or reverse.

Setting

Function

12

Forward jog command: Runs forward at the jog frequency (d1-09).

13

Reverse jog command: Runs in reverse at the jog frequency (d1-09).

D

The forward jog and reverse jog commands have priority over other frequency reference commands.

D

The inverter will stop operation with the stopping method set in b1-03 if the forward jog and reverse

jog commands are both ON for more than 500 ms.

D

Turn ON either the forward jog command or the reverse jog command, not both.

D

These jog commands can operate the Inverter independently. It isn’t necessary for a forward/reverse run

command to be input.

J

Terminal 36/39 Switch: “1F”

D

When this function is set for a multi-function input, that input terminal can be used to switch between

terminal 36 and terminal 39.

OFF

The analog input from terminal 36 is used as the master-speed frequency reference.

ON

The analog input from terminal 39 is used as the master speed frequency reference.

D

When terminal 39 is used as the frequency reference, set “1F” (frequency reference) in constant H3-09;

this constant is the function selector for frequency reference (current) terminal 39. A setting fault

(OPE03) will occur if this function is selected without setting “1F” in H3-09.

D

When H3-09 is set to “1F” (frequency reference) but none of the multi-function inputs is set to “1F”

(terminal 36/39 switch), the sum of the inputs from terminals 36 and 39 will be used as the master-speed

frequency reference.