7.5 Common Functions

7 - 99

7.5.7 Operator Constants: o

J

Operator Display Selection: o1-01 to o1-05

Constant Number Display Selection: o1-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o1-01

Constant No. display

selection

f

4 to 35

--

6

B

B

B

B

D

In operation mode, the frequency reference, output frequency, output current, and output voltage can

be monitored immediately if the factory settings are being used. One of these four values, the output

voltage, can be changed to a different value.

D

When you want to monitor a value other than the output voltage, set that number in constant o1-01.

D

Use the last two digits from the “U1 Monitor” list (U1-jj) to select a value. Refer to Table 4.3.

Monitor Selection After Power Up: o1-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o1-02

Monitor selection af-

ter power up

f

1 to 4

--

1

B

B

B

B

D

When the power is turned on, the frequency reference will appear in the Unit’s data display if the factory

settings are being used.

D

Any one of the four values monitored at startup (frequency reference, output frequency, output current,

or the value set in constant o1-01) can be selected to appear when the power is turned ON.

D

Change the setting of constant o1-02 to display an item other than the frequency reference at startup.

D

Settings

Setting

Function

1

The frequency reference is displayed at start-up.

2

The output frequency is displayed at start-up.

3

The output current is displayed at start-up.

4

The value set in constant o1-01 is displayed at start-up.

Frequency Units of Reference Setting and Monitor: o1-03

D

Set the unit for frequency setting and monitoring.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

o1-03

Frequency units of

reference setting and

monitor

x

0 to 39999

--

0

B

B

B

B

D

Settings

Setting

Unit

0

0.01 Hz

1

0.01%