Conditions for monitoring – Yaskawa G5HHP Drive User Manual

Page 82

Advertising
background image

Setting User Constants

4.2.4 Operation Mode

4 - 14

J

Conditions for Monitoring

Table 4.3 shows the items that can be monitored in operation mode.
The “Valid access levels” column in the table indicates whether an item can be monitored in a particular

access level and control method. The codes in this column have the following meanings.

Q

Items that can be monitored in all access levels (Quick-Start, Basic, and Advanced).

B

Items that can be monitored in the Advanced and Basic access levels.

A

Items that can be monitored only in the Advanced access level.

x

Items that cannot be monitored in the control mode shown.

The output signal levels for multi-function analog outputs shown in the table are for a gain of 100.0 and a

bias of 0.00.

Table 4.3 Constants Monitored in Operation Mode

Con-

Name

Output Signal Levels for

Valid Access Levels

Func-

tion

Con-

stant

No.

Digital Operator

Display

Function

Output Signal Levels for

Multi-function Analog

Outputs

Min.

Unit

V/f

V/f w/

PG

Open

-loop

Vec-

tor

Flux

Vec-

tor

U1-01

Frequency refer-

ence

Monitors/sets the frequency refer-

ence value.
Th displ

nits c n b s t ith

10 V: Max. frequency
(0 to ±10 V possible)

0.01

Hz

Q

Q

Q

Q

U1 01

Frequency Ref

The display units can be set with

user constant o1-03.

(0 to ±10 V possible)

Hz

Q

Q

Q

Q

U1-02

Output frequency

Monitors the output frequency.
The display units can be set with

10 V: Max. frequency

0.01

Q

Q

Q

Q

U1-02

Output Freq

The display units can be set with

user constant o1-03.

10 V: Max. frequency
(0 to ±10 V possible)

0.01

Hz

Q

Q

Q

Q

U1-03

Output current

Monitors the output current

10 V: Rated current

0 1 A

Q

Q

Q

Q

U1-03

Output Current

Monitors the output current.

10 V: Rated current
(0 to +10 V output)

0.1 A

Q

Q

Q

Q

U1-04

Control method

Shows which control mode is set

Can’t be output

Q

Q

Q

Q

U1-04

Control Method

Shows which control mode is set. Can’t be output.

--

Q

Q

Q

Q

U1-05

Motor speed

Monitors the motor speed

10 V: Max. frequency

0.01

X

Q

Q

Q

U1-05

Motor Speed

Monitors the motor speed.

10 V: Max. frequency
(0 to ±10 V possible)

0.01

Hz

X

Q

Q

Q

U1-06

Output voltage

Monitors the Inverter’s internal

10 V: 400 (575) VAC

0 1 V

Q

Q

Q

Q

U1-06

Output Voltage

Monitors the Inverter s internal

output voltage reference value.

10 V: 400 (575) VAC
(0 to +10 V output)

0.1 V

Q

Q

Q

Q

U1-07

DC bus voltage

Monitors the DC voltage of the

10 V: 500 (1040) VDC

1 V

Q

Q

Q

Q

U1-07

DC Bus Voltage

Monitors the DC voltage of the

Inverter’s internal main circuit.

10 V: 500 (1040) VDC
(0 to +10 V output)

1 V

Q

Q

Q

Q

Status

Moni

U1-08

Output power

Monitors the output power. (This

10 V: Max. motor capacity

0 1 kW

Q

Q

Q

Q

Moni-

tor

U1-08

Output kWatts

Monitors the output power. (This

is an internally detected value.)

10 V: Max. motor capacity
(0 to ±10 V possible)

0.1 kW

Q

Q

Q

Q

tor

U1-09

Torque reference

Monitors the internal torque refer-

ence value when vector control is

10 V: Rated torque

0 1 %

X

X

Q

Q

U1-09

Torque Reference

ence value when vector control is

used.

10 V: Rated torque
(0 to ±10 V possible)

0.1 %

X

X

Q

Q

U1-10

Input terminal sta-

tus

Shows input ON/OFF status.

U1-10 = 0 0 0 0 0 0 0 0

1: Terminal 9 ON

1: Terminal 10 ON

1: Terminal 11 ON

Can’t be output.

--

Q

Q

Q

Q

U1 10

Input Term Sts

1: Terminal 12 ON

1: Terminal 13 ON

1: Terminal 14 ON

1: Terminal 15 ON

1: Terminal 16 ON

Can t be output.

--

Q

Q

Q

Q

U1-11

Output terminal

status

Shows output ON/OFF status.

U1-11 = 0 0 0 0 0 0 0 0

1: Terminals 53--57 ON

1: Terminal 19 ON

Can’t be output.

--

Q

Q

Q

Q

U1 11

Output Term Sts

1: Terminal 19 ON

1: Terminal 20 ON

Not used. (always 0)

1: Terminals 25/52--23 ON

Can t be output.

--

Q

Q

Q

Q

4