User Constants

8.2.7 Protection Constants: L

8 - 36

J

Reference Detection: L4

C

t t

Name

S tti

F t

Change

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

L4-01

Speed agree detec-

tion level

Effective when “Desired frequency

(ref/setting) agree 1,” “Frequency

detection 1,” “Frequency detection

2,” are set for multi-function out-

t

0.0 to

150 0

0.0

x

B

B

B

B

7 - 92

L4 01

Spd Agree Level

,

put.
Frequencies to be detected are set

in Hz units.

150.0

0.0

x

B

B

B

B

7 - 92

L4-02

Speed agree detec-

tion width

Effective when “Frequency (ref/

out) agree 1,” “Desired frequency

(ref/setting) agree 1,” “Frequency

detection 1,” “Frequency detection

2”

t f

lti f

ti

t t

0.0 to

20 0

2.0

x

B

B

B

B

7 - 92

L4 02

Spd Agree Width

,

q

y

2” are set for multi-function output.
Sets the frequency detection width

in Hz units.

20.0

2.0

x

B

B

B

B

7 - 92

L4-03

Speed Agree detec-

tion level (+/--)

Effective when “Desired frequency

(ref/setting) agree 2,” “Frequency

detection 3,” “Frequency detection

4,” are set for multi-function out-

t

--150.0

to

0.0

x

A

A

A

A

7 - 92

L4 03

Spd Agree Lvl + --

,

put.
Frequency detection width is set in

Hz units.

to

+150.0

0.0

x

A

A

A

A

7 - 92

L4-04

Speed agree detec-

tion width (+/--)

Effective when “Frequency (ref/

out) agree 2,” “Desired frequency

(ref/setting) agree 1,” “Frequency

detection 3,” “Frequency detection

4”

t f

lti f

ti

t t

0.0 to

20 0

2.0

x

A

A

A

A

7 - 92

L4 04

Spd Agree Wdth + --

,

q

y

4” are set for multi-function output.
Frequency detection width is set in

Hz units.

20.0

2.0

x

A

A

A

A

7 - 92

L4-05

Operation when fre-

quency reference is

missing

0: Stop (Operation follows the fre-

quency reference.)

1: Operation at 80% speed contin-

ues. (At 80% of speed before

the frequency reference was

lost)

0, 1

0

x

A

A

A

A

7 - 92

Ref Loss Sel

lost)

;

Frequency reference is lost: Fre-

quency reference dropped over

90% in 400 ms.

J

Fault Restart: L5

C

t t

Name

S tti

F t

Change

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

L5-01

Number of auto re-

start attempts

Sets the number of auto restart at-

tempts.
Automatically restarts after a fault

0 to 10

0

x

B

B

B

B

7 - 94

L5 01

Num of Restarts

Automatically restarts after a fault

and conducts a speed search from

the run frequency.

0 to 10

0

x

B

B

B

B

7 - 94

L5-02

Auto restart operation

selection

Sets whether a fault contact output

is activated during fault restart.
0: Not output (Fault contact is not

activated )

0, 1

0

x

B

B

B

B

7 - 95

L5 02

Restart Sel

activated.)

1: Output (Fault contact is acti-

vated.)

0, 1

0

x

B

B

B

B

7 - 95

8