Important setting user constants – Yaskawa G5HHP Drive User Manual

Page 102

Advertising
background image

IMPORTANT

Setting User Constants

4.2.7 Autotuning Mode

4 - 34

Step

Remarks

Digital Operator Display

Key Sequence

11

Rated Speed

1750 RPM

12

RESET

DATA

ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of

rated voltage setting.

Note Rated voltage for vector control motors is approx. 10 to 20% lower than general--purpose

motors. Verify motor voltage listed on the nameplate or the test report before use.

Step

Key Sequence

Digital Operator Display

Remarks

13

Number of Poles

4

14

RESET

DATA

ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of

rated voltage setting.

15

Select Motor 1/2

1

16

RESET

DATA
ENTER

DATA

ENTER

Press the keys as in steps 4, 5, 6 of

rated voltage setting.
Leave the setting at 1 to set the value

for motor 1 (the motor contacts normal-

ly used.)
Select “2” to store the autotuning re-

sults for motor 2.

17

Tuning Ready?

Press RUN Key

18

RUN

Tune Processing

Hz A

Autotuning starts and the motor rotates

for approx. one minute.

Tune Successful

Then the motor stops automatically.

19

MENU

G5* Main Menu *

Operation

Returns to the operation mode display.

(1) If a fault occurs during autotuning, refer to Table 5.1 Troubleshooting Autotuning Faults.

(2) Autotuning may not be possible depending on the motor type. For such motors, obtain the electric constants

calculated based on Steinmetz’s constant.