Basic Operation

6.5.5 Adjusting Speed Control (ASR) Gain

6 - 46

4. If the overshooting or undershooting can’t be eliminated by adjusting the gain, decrease the ASR limit

(C5-05) to lower the frequency reference compensation limit.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C5-05

ASR limit

x

0.0 to 20.0

%

5.0

x

A

x

x

•

Since C5-05 can’t be changed during operation, stop the Inverter’s operation and then decrease the

ASR limit by 0.5 (%).

•

Perform step 3 again after the setting has been changed.

•

The ASR limit is the frequency limit for compensation by speed control. Set this frequency limit

as a percentage of the maximum output frequency.

•

If the frequency limit is lowered too much, the motor speed might not reach the target speed. Verify

that the target speed is reached during normal operation.