Appendix

12 - 12

12.7 User Constants

Factory settings are given for a 400-V class Inverter of 200 kW set to open loop vector control (A1-02 = 2).

Table 12.1 User Constants

No.

Name

(Display)

Factory

Setting

Setting

No.

Name

(Display)

Factory

Setting

Setting

A1-00

Language selection for digital operator display

(Select Language)

1

*

1

b6-01

Dwell frequency at start

(Dwell Ref @ Start)

0.0

A1-01

Constant access level

(Access Level)

2

b6-02

Dwell time at start

(Dwell Time @ Start)

0.0

A1-02

Control method selection

(Control Method)

2

*

1

b6-03

Dwell frequency at stop

(Dwell Ref @ Stop)

0.0

A1-03

Initialize

(Init Parameters)

0

b6-04

Dwell time at stop

(Dwell Time @ Stop)

0.0

A1-04

Password 1

(Enter Password)

0

b7-01

Droop control gain

*2

(Droop Gain)

0.0

A1-05

Password 2

(Select Password)

0

b7-02

Droop control delay time

2

(Droop Delay Time)

0.05

A2-01

to

A2-32

User setting constant

(User Pram 1 to 32)

------

b8-01

Energy-saving gain

(Energy Save Gain)

80

b1-01

Reference selection

(Reference Source)

1

b8-02

Energy-saving frequency

(Energy Save Freq)

0.0

b1-02

Operation method selection

(Run Source)

1

b9-01

Zero-servo gain

(Zero Servo Gain)

5

b1-03

Stopping method selection

(Stopping Method)

0

b9-02

Zero-servo completion width

(Zero Servo Count)

10

b1-04

Prohibition of reverse operation

(Reverse Oper)

0

C1-01

Acceleration time 1

(Accel Time 1)

10.0

b1-05

Operation selection for setting of E1-09 or less

(Zero-Speed Oper)

0

C1-02

Deceleration time 1

(Decel Time 1)

10.0

b1-06

Read sequence input twice

(Cntl Input Scans)

1

C1-03

Acceleration time 2

(Accel Time 2)

10.0

b1-07

Operation after switching to remote mode

*2

(LOC/REM RUN Sel)

0

C1-04

Deceleration time 2

(Decel Time 2)

10.0

b2-01

Zero speed level (DC injection braking start fre-

quency)

(DCInj Start Rreq)

0.5

C1-05

Acceleration time 3

(Accel Time 3)

10.0

b2-02

DC injection braking current

(DCinj Current)

50

C1-06

Deceleration time 3

(Decel Time 3)

10.0

b2-03

DC injection braking time at start

(DCInj Time @ Start)

0.00

C1-07

Acceleration time 4

(Accel Time 4)

10.0

b2-04

DC injection braking time at stop

(DCInj Time @ Stop)

0.50

C1-08

Deceleration time 4

(Decel Time 4)

10.0

b3-01

Speed search selection at start

(SpdSrch at Start)

0

*

3

C1-09

Emergency stop time

(Fast Stop Time)

10.0

b3-02

Speed search operating current

(SpdSrch Current)

100

*

3

C1-10

Accel/decel time setting unit

(Acc/Dec Units)

1

b3-03

Speed search deceleration time

(SpdSrch Dec Time)

2.0

C1-11

Accel/decel time switching frequency

(Acc/Dec SW Freq)

0.0

b4-01

Timer function ON-delay time

(Delay-ON Timer)

0.0

C2-01

S-curve characteristic time at acceleration start

(SCrv Acc @ Start)

0.20

b4-02

Timer function OFF-delay time

(Delay-OFF Timer)

0.0

C2-02

S-curve characteristic time at acceleration end

(SCrv Acc @ End)

0.20

b5-01

PID control mode selection

(PID Mode)

0

C2-03

S-curve characteristic time at deceleration start

(SCrv Dec @ Srat)

0.20

b5-02

Proportional gain (P)

(PID Gain)

1.00

C2-04

S-curve characteristic time at deceleration end

(SCrv Dec @ End)

0.00

b5-03

Integral (I) time

(PID I Time)

1.0

C3-01

Slip compensation gain

(Slip Comp Gain)

1.0

*

3

b5-04

Integral (I) limit

(PID I Limit)

100.0

C3-02

Slip compensation primary delay time

(Slip Comp Time)

200

*

3

b5-05

Differential (D) time

(PID D Time)

0.00

C3-03

Slip compensation limit

(Slip Comp Limit)

200

b5-06

PID limit

(PID Limit)

100.0

C3-04

Slip compensation during regeneration

(Slip Comp Regen)

0

b5-07

PID offset adjustment

(PID Offset)

0.0

C3-05

Flux calculation method

(Flux Select)

0

b5-08

PID primary delay time constant

(PID Delay Time)

0.00

C4-01

Torque compensation gain

(Torq Comp Gain)

1.00

12