Yaskawa G5HHP Drive User Manual

Page 124

Advertising
background image

Basic Operation

6.1.2 Frequency Reference Settings: b1-01, H3-01, H3-08, H3-09

6 - 6

Signal Level for Multi-function Analog Input, Terminal 42: H3-04

D

Set the signal level for the multi-function analog input.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-04

Signal level selection

(terminal 42)

x

0, 1

--

0

B

B

B

B

D

Settings

Setting

Function

0

0 to 10 VDC input [11--bit + polarity (positive/negative) input]

1

--10 to 10 VDC input

(A negative voltage is a reference for reverse rotation.)

J

Adjusting Analog Inputs: H3-02, H3-03, H3-06, H3-07, H3-10, H3-11, H3-12

D

There are three constants used to adjust the analog inputs: The gain, bias (both set separately for each

input), and filter time constant (a single value for all of the inputs).

•

The gain and bias can be adjusted separately for each analog input (terminals 36, 39, and 42).

Gain:

Set the frequency corresponding to a 10 V (20 mA) input as a percentage of the

maximum frequency. (The maximum output frequency set in E1-04 is 100%.)

Bias:

Set the frequency corresponding to a 0 V (4 mA) input as a percentage of the

maximum frequency. (The maximum output frequency set in E1-04 is 100%.)

•

Set the gains and biases for terminals 13, 14, and 16 as follows:

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-02

Gain for terminal 36

f

0.0 to

1000.0

%

100.0

B

B

B

B

H3-03

Bias for terminal 36

f

--100.0 to

100.0

%

0.0

B

B

B

B

H3-10

Gain for terminal 39

f

0.0 to

1000.0

%

100.0

A

A

A

A

H3-11

Bias for terminal 39

f

--100.0 to

100.0

%

0.0

A

A

A

A

H3-06

Gain for terminal 42*

f

0.0 to

1000.0

%

100.0

B

B

B

B

H3-07

Bias for terminal 42*

f

--100.0 to

100.0

%

0.0

B

B

B

B

* The settings for terminal 42 are valid only when the multi-function analog input has been se-

lected. The gain and bias set here will be disregarded if a frequency reference is selected and

the values set for terminal 36 will be used.

Frequency

reference

0 V

(4 mA)

10 V

(20 mA)

Use the current values shown in

parentheses when current input

has been selected.

Max. output frequency × Gain

100

Max. output frequency × Bias

100

Fig 6.2

Gain and Bias Chart

6

Advertising