6.1.2 Frequency Reference Settings: b1-01, H3-01, H3-08, H3-09

6 - 6

Signal Level for Multi-function Analog Input, Terminal 42: H3-04

D

Set the signal level for the multi-function analog input.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-04

Signal level selection

(terminal 42)

x

0, 1

--

0

B

B

B

B

D

Settings

Setting

Function

0

0 to 10 VDC input [11--bit + polarity (positive/negative) input]

1

--10 to 10 VDC input

(A negative voltage is a reference for reverse rotation.)

J

Adjusting Analog Inputs: H3-02, H3-03, H3-06, H3-07, H3-10, H3-11, H3-12

D

There are three constants used to adjust the analog inputs: The gain, bias (both set separately for each

input), and filter time constant (a single value for all of the inputs).

The gain and bias can be adjusted separately for each analog input (terminals 36, 39, and 42).

Gain:

Set the frequency corresponding to a 10 V (20 mA) input as a percentage of the

maximum frequency. (The maximum output frequency set in E1-04 is 100%.)

Bias:

Set the frequency corresponding to a 0 V (4 mA) input as a percentage of the

maximum frequency. (The maximum output frequency set in E1-04 is 100%.)

Set the gains and biases for terminals 13, 14, and 16 as follows:

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-02

Gain for terminal 36

f

0.0 to

1000.0

%

100.0

B

B

B

B

H3-03

Bias for terminal 36

f

--100.0 to

100.0

%

0.0

B

B

B

B

H3-10

Gain for terminal 39

f

0.0 to

1000.0

%

100.0

A

A

A

A

H3-11

Bias for terminal 39

f

--100.0 to

100.0

%

0.0

A

A

A

A

H3-06

Gain for terminal 42*

f

0.0 to

1000.0

%

100.0

B

B

B

B

H3-07

Bias for terminal 42*

f

--100.0 to

100.0

%

0.0

B

B

B

B

* The settings for terminal 42 are valid only when the multi-function analog input has been se-

lected. The gain and bias set here will be disregarded if a frequency reference is selected and

the values set for terminal 36 will be used.

Frequency

reference

0 V

(4 mA)

10 V

(20 mA)

Use the current values shown in

parentheses when current input

has been selected.

Max. output frequency × Gain

100

Max. output frequency × Bias

100

Fig 6.2

Gain and Bias Chart

6