Advanced Operation

7.2.1 Energy-saving Control Function

7 - 12

7.2.1 Energy-saving Control Function

The energy-saving control function is enabled when the energy-saving command (setting 63) has been set

in a multi-function input (H1-01 through H1-06). Inputting the energy-saving command while there is a

light load causes the Inverter’s output voltage to be reduced and saves energy. Turn OFF the energy-saving

command when a normal load is added.

J

Energy-saving Gain: b8-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b8-01

Energy-saving gain

x

0 to 100

%

80

A

A

x

x

D

Constant b8-01 determines the Inverter’s output voltage when the energy-saving command is input. Set

this value as a percentage of the V/f pattern’s voltage.

D

Constant L2-04 (the voltage recovery time) determines the rate at which the output voltage is changed

when the energy-saving command is turned ON or OFF.

J

Energy-saving Frequency: b8-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b8-02

Energy-saving fre-

quency

x

0.0 to 150.0

Hz

0.0

A

A

x

x

D

Constant b8-02 determines the lower limit frequency for the energy-saving function.

D

The energy-saving command is enabled only when the frequency reference is above the energy-saving

frequency and the motor speed is within the “speed agree” range.

A time chart for energy-saving operation is shown below.

E1-03 to E1-10 setting × Energy-saving Gain

(b8-01)

Run command

Energy-saving

command

Output frequency

Output voltage

OFF

ON

Frequency reference ≥ b8-02

(energy-saving frequency)

L2-04

(Voltage recovery time)

OFF

ON

Fig 7.4

Time Chart for Energy-saving Operation

7.2.2 Hunting-prevention Function

The hunting-prevention function suppresses hunting when the motor is operating with a light load. This

function is valid with V/f control and V/f with PG feedback control.