2.5 Checking and Controlling the Installation Site

2 - 11

Connection holes for Inverter Panels

(Six 14-dia holes)

Connection holes for other panels

(Eight 14-dia holes)

Fig 2.5

Inverter Panel Side-by-side Connection

The method for connecting Inverter Panels Side-by-side is different from the method for connecting an In-

verter Panel with other panels.

Inverter Panel

Inverter Panel

Inverter Panel

Other panel

(b) Connection with an ordinary panel

(a) Connection with Inverter Panel

M10×90 bolt

Hardwood washer

M10 nut, S washer,

hardwood washer

Mounting frame

Side plate

M10×60 bolt

Hardwood washer

M10 nut, S washer, hard-

wood washer

Mounting frame

Side plate

Fig 2.6

Side-by-side Connection Joint

2.5.6 Tightening Anchor Bolts

When the installation work described in 2.5.5, above, has been completed, secure the Inverter Panel with

four anchor bolts. Perform the foundation work according to the external dimensions drawings provided

by Yaskawa.